WindLookupTableFunctionKind Enum

Function of the lookup table.

Enumeration Values (16)
Value Описание
prr Power versus speed change (negative slip) lookup table (p<sub>rr</sub>(deltaomega)). It is used for the rotor resistance control model, IEC 61400-27-1:2015, 5.6.5.3.
omegap Power vs. speed lookup table (omega(p)). It is used for the P control model type 3, IEC 61400-27-1:2015, 5.6.5.4.
ipmax Lookup table for voltage dependency of active current limits (i<sub>pmax</sub>(u<sub>WT</sub>)). It is used for the current limitation model, IEC 61400-27-1:2015, 5.6.5.8.
iqmax Lookup table for voltage dependency of reactive current limits (i<sub>qmax</sub>(u<sub>WT</sub>)). It is used for the current limitation model, IEC 61400-27-1:2015, 5.6.5.8.
pwp Power vs. frequency lookup table (p<sub>WPbias</sub>(f)). It is used for the wind power plant frequency and active power control model, IEC 61400-27-1:2015, Annex D.
tcwdu Crowbar duration versus voltage variation look-up table (T<sub>CW</sub>(du)). It is a case-dependent parameter. It is used for the type 3B generator set model, IEC 61400-27-1:2015, 5.6.3.3.
tduwt Lookup table to determine the duration of the power reduction after a voltage dip, depending on the size of the voltage dip (T<sub>d</sub>(u<sub>WT</sub>)). It is a type-dependent parameter. It is used for the pitch control power model, IEC 61400-27-1:2015, 5.6.5.1.
qmaxp Lookup table for active power dependency of reactive power maximum limit (q<sub>maxp</sub>(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
qminp Lookup table for active power dependency of reactive power minimum limit (q<sub>minp</sub>(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
qmaxu Lookup table for voltage dependency of reactive power maximum limit (q<sub>maxu</sub>(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
qminu Lookup table for voltage dependency of reactive power minimum limit (q<sub>minu</sub>(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10.
tuover Disconnection time versus over-voltage lookup table (T<sub>uover</sub>(u<sub>WT</sub>)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
tuunder Disconnection time versus under-voltage lookup table (T<sub>uunder</sub>(u<sub>WT</sub>)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
tfover Disconnection time versus over-frequency lookup table (T<sub>fover</sub>(f<sub>WT</sub>)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
tfunder Disconnection time versus under-frequency lookup table (T<sub>funder</sub>(f<sub>WT</sub>)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6.
qwp Look up table for the UQ static mode (q<sub>WP</sub>(u<sub>err</sub>)). It is used for the voltage and reactive power control model, IEC 61400-27-1:2015, Annex D.
Ссылки (1)
Класс Свойство Описание
cim:WindDynamicsLookupTable cim:lookupTableFunctionType

Type of the lookup table function.

Информация о классе
ID
cim:WindLookupTableFunctionKind
Тип
Enum
Значений
16