WindLookupTableFunctionKind Enum
Function of the lookup table.
Enumeration Values (16)
| Value | Описание |
|---|---|
prr
|
Power versus speed change (negative slip) lookup table (p<sub>rr</sub>(deltaomega)). It is used for the rotor resistance control model, IEC 61400-27-1:2015, 5.6.5.3. |
omegap
|
Power vs. speed lookup table (omega(p)). It is used for the P control model type 3, IEC 61400-27-1:2015, 5.6.5.4. |
ipmax
|
Lookup table for voltage dependency of active current limits (i<sub>pmax</sub>(u<sub>WT</sub>)). It is used for the current limitation model, IEC 61400-27-1:2015, 5.6.5.8. |
iqmax
|
Lookup table for voltage dependency of reactive current limits (i<sub>qmax</sub>(u<sub>WT</sub>)). It is used for the current limitation model, IEC 61400-27-1:2015, 5.6.5.8. |
pwp
|
Power vs. frequency lookup table (p<sub>WPbias</sub>(f)). It is used for the wind power plant frequency and active power control model, IEC 61400-27-1:2015, Annex D. |
tcwdu
|
Crowbar duration versus voltage variation look-up table (T<sub>CW</sub>(du)). It is a case-dependent parameter. It is used for the type 3B generator set model, IEC 61400-27-1:2015, 5.6.3.3. |
tduwt
|
Lookup table to determine the duration of the power reduction after a voltage dip, depending on the size of the voltage dip (T<sub>d</sub>(u<sub>WT</sub>)). It is a type-dependent parameter. It is used for the pitch control power model, IEC 61400-27-1:2015, 5.6.5.1. |
qmaxp
|
Lookup table for active power dependency of reactive power maximum limit (q<sub>maxp</sub>(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10. |
qminp
|
Lookup table for active power dependency of reactive power minimum limit (q<sub>minp</sub>(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10. |
qmaxu
|
Lookup table for voltage dependency of reactive power maximum limit (q<sub>maxu</sub>(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10. |
qminu
|
Lookup table for voltage dependency of reactive power minimum limit (q<sub>minu</sub>(p)). It is used for the QP and QU limitation model, IEC 61400-27-1:2015, 5.6.5.10. |
tuover
|
Disconnection time versus over-voltage lookup table (T<sub>uover</sub>(u<sub>WT</sub>)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6. |
tuunder
|
Disconnection time versus under-voltage lookup table (T<sub>uunder</sub>(u<sub>WT</sub>)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6. |
tfover
|
Disconnection time versus over-frequency lookup table (T<sub>fover</sub>(f<sub>WT</sub>)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6. |
tfunder
|
Disconnection time versus under-frequency lookup table (T<sub>funder</sub>(f<sub>WT</sub>)). It is used for the grid protection model, IEC 61400-27-1:2015, 5.6.6. |
qwp
|
Look up table for the UQ static mode (q<sub>WP</sub>(u<sub>err</sub>)). It is used for the voltage and reactive power control model, IEC 61400-27-1:2015, Annex D. |
Ссылки (1)
| Класс | Свойство | Описание |
|---|---|---|
| cim:WindDynamicsLookupTable | cim:lookupTableFunctionType |
Type of the lookup table function. |
Информация о классе
- ID
cim:WindLookupTableFunctionKind- Тип
- Enum
- Значений
- 16