LoadComposite Class

Combined static load and induction motor load effects. The dynamics of the motor are simplified by linearizing the induction machine equations.

Diagram
Свойства (11)
ID Тип Описание Количество
epvs Float Active load-voltage dependence index (static) (<i>Epvs</i>). Typical value = 0,7. 1..1
epfs Float Active load-frequency dependence index (static) (<i>Epfs</i>). Typical value = 1,5. 1..1
eqvs Float Reactive load-voltage dependence index (static) (<i>Eqvs</i>). Typical value = 2. 1..1
eqfs Float Reactive load-frequency dependence index (static) (<i>Eqfs</i>). Typical value = 0. 1..1
epvd Float Active load-voltage dependence index (dynamic) (<i>Epvd</i>). Typical value = 0,7. 1..1
epfd Float Active load-frequency dependence index (dynamic) (<i>Epfd</i>). Typical value = 1,5. 1..1
eqvd Float Reactive load-voltage dependence index (dynamic) (<i>Eqvd</i>). Typical value = 2. 1..1
eqfd Float Reactive load-frequency dependence index (dynamic) (<i>Eqfd</i>). Typical value = 0. 1..1
lfac Float Loading factor (<i>L</i><i><sub>fac</sub></i>). The ratio of initial <i>P</i> to motor MVA base. Typical value = 0,8. 1..1
h Seconds Inertia constant (<i>H</i>) (&gt;= 0). Typical value = 2,5. 1..1
pfrac Float Fraction of constant-power load to be represented by this motor model (<i>P</i><i><sub>FRAC</sub></i>) (&gt;= 0,0 and &lt;= 1,0). Typical value = 0,5. 1..1
Информация о классе
ID
cim:LoadComposite
Тип
Class
Наследует
cim:LoadDynamics
Свойств
11