OverexcLim2 Class

Different from LimIEEEOEL, LimOEL2 has a fixed pickup threshold and reduces the excitation set-point by means of a non-windup integral regulator. <i>Irated</i> is the rated machine excitation current (calculated from nameplate conditions: <i>V</i><i><sub>nom</sub></i>, <i>P</i><i><sub>nom</sub></i>, <i>CosPhi</i><i><sub>nom</sub></i>).

Diagram
Свойства (4)
ID Тип Описание Количество
koi PU Gain Over excitation limiter (<i>K</i><i><sub>OI</sub></i>). Typical value = 0,1. 1..1
voimax PU Maximum error signal (<i>V</i><i><sub>OIMAX</sub></i>) (&gt; OverexcLim2.voimin). Typical value = 0. 1..1
voimin PU Minimum error signal (<i>V</i><i><sub>OIMIN</sub></i>) (&lt; OverexcLim2.voimax). Typical value = -9999. 1..1
ifdlim PU Limit value of rated field current (<i>I</i><i><sub>FDLIM</sub></i>). Typical value = 1,05. 1..1
Информация о классе
ID
cim:OverexcLim2
Тип
Class
Наследует
cim:OverexcitationLimiterDynamics
Свойств
4