CurrentFlow Data Type
Electrical current with sign convention: positive flow is out of the conducting equipment into the connectivity node. Can be both AC and DC.
Ссылки (16)
| Класс | Свойство | Описание |
|---|---|---|
| cim:BusbarSection | cim:ipMax |
Maximum allowable peak short-circuit current of busbar (Ipmax in IEC 60909-0). Mechanical limit of the busbar in the substation itself. Used for short circuit data exchange according to IEC 60909. |
| cim:ExternalNetworkInjection | cim:maxInitialSymShCCurrent |
Maximum initial symmetrical short-circuit currents (Ik" max) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909. |
| cim:ExternalNetworkInjection | cim:minInitialSymShCCurrent |
Minimum initial symmetrical short-circuit currents (Ik" min) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909. |
| cim:PetersenCoil | cim:offsetCurrent |
The offset current that the Petersen coil controller is operating from the resonant point. This is normally a fixed amount for which the controller is configured and could be positive or negative. Typically 0 to 60 A depending on voltage and resonance conditions. |
| cim:PetersenCoil | cim:positionCurrent |
The control current used to control the Petersen coil also known as the position current. Typically in the range of 20 mA to 200 mA. |
| cim:PowerTransformer | cim:beforeShCircuitHighestOperatingCurrent |
The highest operating current (Ib in IEC 60909-0) before short circuit (depends on network configuration and relevant reliability philosophy). It is used for calculation of the impedance correction factor KT defined in IEC 60909-0. |
| cim:SeriesCompensator | cim:varistorRatedCurrent |
The maximum current the varistor is designed to handle at specified duration. It is used for short circuit calculations and exchanged only if SeriesCompensator.varistorPresent is true. The attribute shall be a positive value. |
| cim:SynchronousMachine | cim:ikk |
Steady-state short-circuit current (in A for the profile) of generator with compound excitation during 3-phase short circuit. - Ikk=0: Generator with no compound excitation. - Ikk<>0: Generator with compound excitation. Ikk is used to calculate the minimum steady-state short-circuit current for generators with compound excitation. (4.6.1.2 in IEC 60909-0:2001). Used only for single fed short circuit on a generator. (4.3.4.2. in IEC 60909-0:2001). |
| cim:ACDCConverter | cim:idc |
Converter DC current, also called Id. It is converter’s state variable, result from power flow. |
| cim:CsConverter | cim:maxIdc |
The maximum direct current (Id) on the DC side at which the converter should operate. It is converter’s configuration data use in power flow. The attribute shall be a positive value. |
| cim:CsConverter | cim:minIdc |
The minimum direct current (Id) on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value. |
| cim:CsConverter | cim:ratedIdc |
Rated converter DC current, also called IdN. The attribute shall be a positive value. It is converter’s configuration data used in power flow. |
| cim:CsConverter | cim:targetIdc |
DC current target value. It is converter’s control variable used in power flow. The attribute shall be a positive value. |
| cim:Switch | cim:ratedCurrent |
The maximum continuous current carrying capacity in amps governed by the device material and construction. The attribute shall be a positive value. |
| cim:CurrentLimit | cim:normalValue |
The normal value for limit on current flow. The attribute shall be a positive value or zero. |
| cim:CurrentLimit | cim:value |
Limit on current flow. The attribute shall be a positive value or zero. |