SynchronousMachine Class

An electromechanical device that operates with shaft rotating synchronously with the network. It is a single machine operating either as a generator or synchronous condenser or pump.

Diagram
Легендассылка на enumссылка на класспростое свойствоSynchronousMachinecim:earthing : Booleancim:earthingStarPointR : Resistancecim:earthingStarPointX : Reactancecim:ikk : CurrentFlowcim:mu : Floatcim:x0 : Reactancecim:r0 : Resistancecim:x2 : Reactancecim:r2 : Resistancecim:r : Resistancecim:satDirectSubtransX : PUcim:satDirectSyncX : PUcim:satDirectTransX : PUcim:shortCircuitRotorType : ShortCircuitRotorKindcim:voltageRegulationRange : PerCentcim:SynchronousMachineDynamics : SynchronousMachineDynamicscim:InitialReactiveCapabilityCurve : ReactiveCapabilityCurvecim:maxQ : ReactivePowercim:minQ : ReactivePowercim:qPercent : PerCentcim:type : SynchronousMachineKindcim:operatingMode : SynchronousMachineOperatingModecim:referencePriority : IntegerShortCircuitRotorKindsalientPole1salientPole2turboSeries1turboSeries2SynchronousMachineDynamicsReactiveCapabilityCurveSynchronousMachineKindgeneratorcondensergeneratorOrCondensermotorgeneratorOrMotormotorOrCondensergeneratorOrCondenserOrMotorSynchronousMachineOperatingModegeneratorcondensermotorRotatingMachinecim:GeneratingUnit : GeneratingUnitcim:HydroPump : HydroPumpcim:ratedPowerFactor : Floatcim:ratedS : ApparentPowercim:ratedU : Voltagecim:p : ActivePowercim:q : ReactivePowerRegulatingCondEqcim:RegulatingControl : RegulatingControlcim:controlEnabled : BooleanEnergyConnectionConductingEquipmentcim:Terminals : Terminalcim:SvStatus : SvStatuscim:BaseVoltage : BaseVoltageEquipmentcim:EquipmentContainer : EquipmentContainercim:aggregate : Booleancim:normallyInService : Booleancim:OperationalLimitSet : OperationalLimitSetcim:inService : BooleanPowerSystemResourcecim:Controls : Controlcim:Measurements : Measurementcim:Location : LocationIdentifiedObjectcim:DiagramObjects : DiagramObjectcim:mRID : Stringcim:name : Stringcim:description : Stringcim:energyIdentCodeEic : Stringcim:shortName : String
Свойства (23)
ID Тип Описание Количество
earthing Boolean Indicates whether or not the generator is earthed. Used for short circuit data exchange according to IEC 60909. 1..1
earthingStarPointR Resistance Generator star point earthing resistance (Re). Used for short circuit data exchange according to IEC 60909. 0..1
earthingStarPointX Reactance Generator star point earthing reactance (Xe). Used for short circuit data exchange according to IEC 60909. 0..1
ikk CurrentFlow Steady-state short-circuit current (in A for the profile) of generator with compound excitation during 3-phase short circuit. - Ikk=0: Generator with no compound excitation. - Ikk<>0: Generator with compound excitation. Ikk is used to calculate the minimum steady-state short-circuit current for generators with compound excitation. (4.6.1.2 in IEC 60909-0:2001). Used only for single fed short circuit on a generator. (4.3.4.2. in IEC 60909-0:2001). 0..1
mu Float Factor to calculate the breaking current (Section 4.5.2.1 in IEC 60909-0). Used only for single fed short circuit on a generator (Section 4.3.4.2. in IEC 60909-0). 0..1
x0 Reactance Zero sequence reactance of the synchronous machine. 1..1
r0 Resistance Zero sequence resistance of the synchronous machine. 1..1
x2 Reactance Negative sequence reactance. 1..1
r2 Resistance Negative sequence resistance. 1..1
r Resistance Equivalent resistance (RG) of generator. RG is considered for the calculation of all currents, except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909. 1..1
satDirectSubtransX PU Direct-axis subtransient reactance saturated, also known as Xd"sat. 1..1
satDirectSyncX PU Direct-axes saturated synchronous reactance (xdsat); reciprocal of short-circuit ration. Used for short circuit data exchange, only for single fed short circuit on a generator. (4.3.4.2. in IEC 60909-0:2001). 0..1
satDirectTransX PU Saturated Direct-axis transient reactance. The attribute is primarily used for short circuit calculations according to ANSI. 0..1
shortCircuitRotorType ShortCircuitRotorKind Type of rotor, used by short circuit applications, only for single fed short circuit according to IEC 60909. 0..1
voltageRegulationRange PerCent Range of generator voltage regulation (PG in IEC 60909-0) used for calculation of the impedance correction factor KG defined in IEC 60909-0. This attribute is used to describe the operating voltage of the generating unit. 0..1
SynchronousMachineDynamics SynchronousMachineDynamics Synchronous machine dynamics model used to describe dynamic behaviour of this synchronous machine. 0..1
InitialReactiveCapabilityCurve ReactiveCapabilityCurve The default reactive capability curve for use by a synchronous machine. 0..1
maxQ ReactivePower Maximum reactive power limit. This is the maximum (nameplate) limit for the unit. 0..1
minQ ReactivePower Minimum reactive power limit for the unit. 0..1
qPercent PerCent Part of the coordinated reactive control that comes from this machine. The attribute is used as a participation factor not necessarily summing up to 100% for the participating devices in the control. 0..1
type SynchronousMachineKind Modes that this synchronous machine can operate in. 1..1
operatingMode SynchronousMachineOperatingMode Current mode of operation. 1..1
referencePriority Integer Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on. 1..1
Ссылки (2)
Класс Свойство Описание
cim:SynchronousMachineDynamics cim:SynchronousMachine

Synchronous machine to which synchronous machine dynamics model applies.

cim:ReactiveCapabilityCurve cim:InitiallyUsedBySynchronousMachines

Synchronous machines using this curve as default.

Информация о классе
ID
cim:SynchronousMachine
Тип
Class
Наследует
cim:RotatingMachine
Свойств
23