ExcDC2A.ke

Exciter constant related to self-excited field (<i>Ke</i>). If <i>Ke</i> is entered as zero, the model calculates an effective value of <i>Ke</i> such that the initial condition value of <i>Vr</i> is zero. The zero value of <i>Ke</i> is not changed. If <i>Ke</i> is entered as non-zero, its value is used directly, without change. Typical value = 1.

Информация о свойстве
ID
ExcDC2A.ke
Класс
cim:ExcDC2A Modified IEEE DC2A direct current commutator exciter with speed input, one more leg block in feedback loop and without underexcitation limiters (UEL) inputs. DC type 2 excitation system model with added speed multiplier, added lead-lag, and voltage-dependent limits.
Тип
PU Per Unit - a positive or negative value referred to a defined base. Values typically range from -10 to +10.
Количество
1..1