ExcAC1A Class

Modified IEEE AC1A alternator-supplied rectifier excitation system with different rate feedback source.

Diagram
Свойства (22)
ID Тип Описание Количество
tb Seconds Voltage regulator time constant (<i>Tb</i>) (&gt;= 0). Typical value = 0. 1..1
tc Seconds Voltage regulator time constant (<i>T</i><i><sub>c</sub></i>) (&gt;= 0). Typical value = 0. 1..1
ka PU Voltage regulator gain (<i>Ka</i>) (&gt; 0). Typical value = 400. 1..1
ta Seconds Voltage regulator time constant (<i>Ta</i>) (&gt; 0). Typical value = 0,02. 1..1
vamax PU Maximum voltage regulator output (<i>V</i><i><sub>amax</sub></i>) (&gt; 0). Typical value = 14,5. 1..1
vamin PU Minimum voltage regulator output (<i>V</i><i><sub>amin</sub></i>) (&lt; 0). Typical value = -14,5. 1..1
te Seconds Exciter time constant, integration rate associated with exciter control (<i>Te</i>) (&gt; 0). Typical value = 0,8. 1..1
kf PU Excitation control system stabilizer gains (<i>Kf</i>) (&gt;= 0). Typical value = 0,03. 1..1
kf1 PU Coefficient to allow different usage of the model (<i>Kf1</i>) (&gt;= 0). Typical value = 0. 1..1
kf2 PU Coefficient to allow different usage of the model (<i>Kf2</i>) (&gt;= 0). Typical value = 1. 1..1
ks PU Coefficient to allow different usage of the model-speed coefficient (<i>Ks</i>) (&gt;= 0). Typical value = 0. 1..1
tf Seconds Excitation control system stabilizer time constant (<i>Tf</i>) (&gt; 0). Typical value = 1. 1..1
kc PU Rectifier loading factor proportional to commutating reactance (<i>Kc</i>) (&gt;= 0). Typical value = 0,2. 1..1
kd PU Demagnetizing factor, a function of exciter alternator reactances (<i>Kd</i>) (&gt;= 0). Typical value = 0,38. 1..1
ke PU Exciter constant related to self-excited field (<i>Ke</i>). Typical value = 1. 1..1
ve1 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve1</i>) (&gt; 0). Typical value = 4,18. 1..1
seve1 Float Exciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>1</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>1</sub></i><i>]</i>) (&gt;= 0). Typical value = 0,1. 1..1
ve2 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve2</i>) (&gt; 0). Typical value = 3,14. 1..1
seve2 Float Exciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>2</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>2</sub></i><i>]</i>) (&gt;= 0). Typical value = 0,03. 1..1
vrmax PU Maximum voltage regulator outputs (<i>Vrmax</i>) (&gt; 0). Typical value = 6,03. 1..1
vrmin PU Minimum voltage regulator outputs (<i>Vrmin</i>) (&lt; 0). Typical value = -5,43. 1..1
hvlvgates Boolean Indicates if both HV gate and LV gate are active (<i>HVLVgates</i>). true = gates are used false = gates are not used. Typical value = true. 1..1
Информация о классе
ID
cim:ExcAC1A
Тип
Class
Наследует
cim:ExcitationSystemDynamics
Свойств
22