ExcAC2A Class

Modified IEEE AC2A alternator-supplied rectifier excitation system with different field current limit.

Diagram
Свойства (28)
ID Тип Описание Количество
tb Seconds Voltage regulator time constant (<i>Tb</i>) (&gt;= 0). Typical value = 0. 1..1
tc Seconds Voltage regulator time constant (<i>Tc</i>) (&gt;= 0). Typical value = 0. 1..1
ka PU Voltage regulator gain (<i>Ka</i>) (&gt; 0). Typical value = 400. 1..1
ta Seconds Voltage regulator time constant (<i>Ta</i>) (&gt; 0). Typical value = 0,02. 1..1
vamax PU Maximum voltage regulator output (<i>Vamax</i>) (&gt; 0). Typical value = 8. 1..1
vamin PU Minimum voltage regulator output (<i>Vamin</i>) (&lt; 0). Typical value = -8. 1..1
kb PU Second stage regulator gain (<i>Kb</i>) (&gt; 0). Exciter field current controller gain. Typical value = 25. 1..1
kb1 PU Second stage regulator gain (<i>Kb1</i>). It is exciter field current controller gain used as alternative to <i>Kb</i> to represent a variant of the ExcAC2A model. Typical value = 25. 1..1
vrmax PU Maximum voltage regulator outputs (<i>Vrmax</i>) (&gt; 0). Typical value = 105. 1..1
vrmin PU Minimum voltage regulator outputs (<i>Vrmin</i>) (&lt; 0). Typical value = -95. 1..1
te Seconds Exciter time constant, integration rate associated with exciter control (<i>Te</i>) (&gt; 0). Typical value = 0,6. 1..1
vfemax PU Exciter field current limit reference (<i>Vfemax</i>) (&gt;= 0). Typical value = 4,4. 1..1
kh PU Exciter field current feedback gain (<i>Kh</i>) (&gt;= 0). Typical value = 1. 1..1
kf PU Excitation control system stabilizer gains (<i>Kf</i>) (&gt;= 0). Typical value = 0,03. 1..1
kl PU Exciter field current limiter gain (<i>Kl</i>). Typical value = 10. 1..1
vlr PU Maximum exciter field current (<i>Vlr</i>) (&gt; 0). Typical value = 4,4. 1..1
kl1 PU Coefficient to allow different usage of the model (<i>Kl1</i>). Typical value = 1. 1..1
ks PU Coefficient to allow different usage of the model-speed coefficient (<i>Ks</i>) (&gt;= 0). Typical value = 0. 1..1
tf Seconds Excitation control system stabilizer time constant (<i>Tf</i>) (&gt; 0). Typical value = 1. 1..1
kc PU Rectifier loading factor proportional to commutating reactance (<i>Kc</i>) (&gt;= 0). Typical value = 0,28. 1..1
kd PU Demagnetizing factor, a function of exciter alternator reactances (<i>Kd</i>) (&gt;= 0). Typical value = 0,35. 1..1
ke PU Exciter constant related to self-excited field (<i>Ke</i>). Typical value = 1. 1..1
ve1 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>1</sub></i>) (&gt; 0). Typical value = 4,4. 1..1
seve1 Float Exciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>1</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>1</sub></i><i>]</i>) (&gt;= 0). Typical value = 0,037. 1..1
ve2 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>2</sub></i>) (&gt; 0). Typical value = 3,3. 1..1
seve2 Float Exciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>2</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>2</sub></i><i>]</i>) (&gt;= 0). Typical value = 0,012. 1..1
hvgate Boolean Indicates if HV gate is active (<i>HVgate</i>). true = gate is used false = gate is not used. Typical value = true. 1..1
lvgate Boolean Indicates if LV gate is active (<i>LVgate</i>). true = gate is used false = gate is not used. Typical value = true. 1..1
Информация о классе
ID
cim:ExcAC2A
Тип
Class
Наследует
cim:ExcitationSystemDynamics
Свойств
28