ExcAC3A Class

Modified IEEE AC3A alternator-supplied rectifier excitation system with different field current limit.

Diagram
Свойства (26)
ID Тип Описание Количество
tb Seconds Voltage regulator time constant (<i>Tb</i>) (&gt;= 0). Typical value = 0. 1..1
tc Seconds Voltage regulator time constant (<i>Tc</i>) (&gt;= 0). Typical value = 0. 1..1
ka Seconds Voltage regulator gain (<i>Ka</i>) (&gt; 0). Typical value = 45,62. 1..1
ta PU Voltage regulator time constant (<i>Ta</i>) (&gt; 0). Typical value = 0,013. 1..1
vamax PU Maximum voltage regulator output (<i>Vamax</i>) (&gt; 0). Typical value = 1. 1..1
vamin PU Minimum voltage regulator output (<i>Vamin</i>) (&lt; 0). Typical value = -0,95. 1..1
te Seconds Exciter time constant, integration rate associated with exciter control (<i>Te</i>) (&gt; 0). Typical value = 1,17. 1..1
vemin PU Minimum exciter voltage output (<i>Vemin</i>) (&lt;= 0). Typical value = 0. 1..1
kr PU Constant associated with regulator and alternator field power supply (<i>Kr</i>) (&gt; 0). Typical value =3,77. 1..1
kf PU Excitation control system stabilizer gains (<i>Kf</i>) (&gt;= 0). Typical value = 0,143. 1..1
tf Seconds Excitation control system stabilizer time constant (<i>Tf</i>) (&gt; 0). Typical value = 1. 1..1
kn PU Excitation control system stabilizer gain (<i>Kn</i>) (&gt;= 0). Typical value =0,05. 1..1
efdn PU Value of <i>Efd </i>at which feedback gain changes (<i>Efdn</i>) (&gt; 0). Typical value = 2,36. 1..1
kc PU Rectifier loading factor proportional to commutating reactance (<i>Kc</i>) (&gt;= 0). Typical value = 0,104. 1..1
kd PU Demagnetizing factor, a function of exciter alternator reactances (<i>Kd</i>) (&gt;= 0). Typical value = 0,499. 1..1
ke PU Exciter constant related to self-excited field (<i>Ke</i>). Typical value = 1. 1..1
klv PU Gain used in the minimum field voltage limiter loop (<i>Klv</i>). Typical value = 0,194. 1..1
kf1 PU Coefficient to allow different usage of the model (<i>Kf1</i>). Typical value = 1. 1..1
kf2 PU Coefficient to allow different usage of the model (<i>Kf2</i>). Typical value = 0. 1..1
ks PU Coefficient to allow different usage of the model-speed coefficient (<i>Ks</i>). Typical value = 0. 1..1
vfemax PU Exciter field current limit reference (<i>Vfemax</i>) (&gt;= 0). Typical value = 16. 1..1
ve1 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>1</sub></i>) (&gt; 0). Typical value = 6.24. 1..1
seve1 Float Exciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>1</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>1</sub></i><i>]</i>) (&gt;= 0). Typical value = 1,143. 1..1
ve2 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>2</sub></i>) (&gt; 0). Typical value = 4,68. 1..1
seve2 Float Exciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>2</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>2</sub></i><i>]</i>) (&gt;= 0). Typical value = 0,1. 1..1
vlv PU Field voltage used in the minimum field voltage limiter loop (<i>Vlv</i>). Typical value = 0,79. 1..1
Информация о классе
ID
cim:ExcAC3A
Тип
Class
Наследует
cim:ExcitationSystemDynamics
Свойств
26