ExcAC8B Class

Modified IEEE AC8B alternator-supplied rectifier excitation system with speed input and input limiter.

Diagram
Свойства (27)
ID Тип Описание Количество
inlim Boolean Input limiter indicator. true = input limiter <i>Vimax</i> and <i>Vimin</i> is considered false = input limiter <i>Vimax </i>and <i>Vimin</i> is not considered. Typical value = true. 1..1
ka PU Voltage regulator gain (<i>Ka</i>) (&gt; 0). Typical value = 1. 1..1
kc PU Rectifier loading factor proportional to commutating reactance (<i>Kc</i>) (&gt;= 0). Typical value = 0,55. 1..1
kd PU Demagnetizing factor, a function of exciter alternator reactances (<i>Kd</i>) (&gt;= 0). Typical value = 1,1. 1..1
kdr PU Voltage regulator derivative gain (<i>Kdr</i>) (&gt;= 0). Typical value = 10. 1..1
ke PU Exciter constant related to self-excited field (<i>Ke</i>). Typical value = 1. 1..1
kir PU Voltage regulator integral gain (<i>Kir</i>) (&gt;= 0). Typical value = 5. 1..1
kpr PU Voltage regulator proportional gain (<i>Kpr</i>) (&gt; 0 if ExcAC8B.kir = 0). Typical value = 80. 1..1
ks PU Coefficient to allow different usage of the model-speed coefficient (<i>Ks</i>). Typical value = 0. 1..1
pidlim Boolean PID limiter indicator. true = input limiter <i>Vpidmax</i> and <i>Vpidmin</i> is considered false = input limiter <i>Vpidmax</i> and <i>Vpidmin</i> is not considered. Typical value = true. 1..1
seve1 Float Exciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>1</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>1</sub></i><i>]</i>) (&gt;= 0). Typical value = 0,3. 1..1
seve2 Float Exciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>2</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>2</sub></i><i>]</i>) (&gt;= 0). Typical value = 3. 1..1
ta Seconds Voltage regulator time constant (<i>Ta</i>) (&gt;= 0). Typical value = 0. 1..1
tdr Seconds Lag time constant (<i>Tdr</i>) (&gt; 0 if ExcAC8B.kdr &gt; 0). Typical value = 0,1. 1..1
te Seconds Exciter time constant, integration rate associated with exciter control (<i>Te</i>) (&gt; 0). Typical value = 1,2. 1..1
telim Boolean Selector for the limiter on the block (<i>1/sTe</i>). See diagram for meaning of true and false. Typical value = false. 1..1
ve1 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>1</sub></i>) (&gt; 0). Typical value = 6,5. 1..1
ve2 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>2</sub></i>) (&gt; 0). Typical value = 9. 1..1
vemin PU Minimum exciter voltage output (<i>Vemin</i>) (&lt;= 0). Typical value = 0. 1..1
vfemax PU Exciter field current limit reference (<i>Vfemax</i>). Typical value = 6. 1..1
vimax PU Input signal maximum (<i>Vimax</i>) (&gt; ExcAC8B.vimin). Typical value = 35. 1..1
vimin PU Input signal minimum (<i>Vimin</i>) (&lt; ExcAC8B.vimax). Typical value = -10. 1..1
vpidmax PU PID maximum controller output (<i>Vpidmax</i>) (&gt; ExcAC8B.vpidmin). Typical value = 35. 1..1
vpidmin PU PID minimum controller output (<i>Vpidmin</i>) (&lt; ExcAC8B.vpidmax). Typical value = -10. 1..1
vrmax PU Maximum voltage regulator output (<i>Vrmax</i>) (&gt; 0). Typical value = 35. 1..1
vrmin PU Minimum voltage regulator output (<i>Vrmin</i>) (&lt; 0). Typical value = 0. 1..1
vtmult Boolean Multiply by generator's terminal voltage indicator. true =the limits <i>Vrmax</i> and <i>Vrmin</i> are multiplied by the generator’s terminal voltage to represent a thyristor power stage fed from the generator terminals false = limits are not multiplied by generator's terminal voltage. Typical value = false. 1..1
Информация о классе
ID
cim:ExcAC8B
Тип
Class
Наследует
cim:ExcitationSystemDynamics
Свойств
27