ExcBBC Class

Transformer fed static excitation system (static with ABB regulator). This model represents a static excitation system in which a gated thyristor bridge fed by a transformer at the main generator terminals feeds the main generator directly.

Diagram
Свойства (11)
ID Тип Описание Количество
t1 Seconds Controller time constant (<i>T1</i>) (&gt;= 0). Typical value = 6. 1..1
t2 Seconds Controller time constant (<i>T2</i>) (&gt;= 0). Typical value = 1. 1..1
t3 Seconds Lead/lag time constant (<i>T3</i>) (&gt;= 0). If = 0, block is bypassed. Typical value = 0,05. 1..1
t4 Seconds Lead/lag time constant (<i>T4</i>) (&gt;= 0). If = 0, block is bypassed. Typical value = 0,01. 1..1
k PU Steady state gain (<i>K</i>) (not = 0). Typical value = 300. 1..1
vrmin PU Minimum control element output (<i>Vrmin</i>) (&lt; ExcBBC.vrmax). Typical value = -5. 1..1
vrmax PU Maximum control element output (<i>Vrmax</i>) (&gt; ExcBBC.vrmin). Typical value = 5. 1..1
efdmin PU Minimum open circuit exciter voltage (<i>Efdmin</i>) (&lt; ExcBBC.efdmax). Typical value = -5. 1..1
efdmax PU Maximum open circuit exciter voltage (<i>Efdmax</i>) (&gt; ExcBBC.efdmin). Typical value = 5. 1..1
xe PU Effective excitation transformer reactance (<i>Xe</i>) (&gt;= 0). <i>Xe</i> models the regulation of the transformer/rectifier unit. Typical value = 0,05. 1..1
switch Boolean Supplementary signal routing selector (<i>switch</i>). true = <i>Vs</i> connected to 3rd summing point false = <i>Vs</i> connected to 1st summing point (see diagram). Typical value = false. 1..1
Информация о классе
ID
cim:ExcBBC
Тип
Class
Наследует
cim:ExcitationSystemDynamics
Свойств
11