ExcELIN2 Class

Detailed excitation system ELIN (VATECH). This model represents an all-static excitation system. A PI voltage controller establishes a desired field current set point for a proportional current controller. The integrator of the PI controller has a follow-up input to match its signal to the present field current. Power system stabilizer models used in conjunction with this excitation system model: PssELIN2, PssIEEE2B, Pss2B.

Diagram
Свойства (27)
ID Тип Описание Количество
k1 PU Voltage regulator input gain (<i>K1</i>). Typical value = 0. 1..1
k1ec PU Voltage regulator input limit (<i>K1ec</i>). Typical value = 2. 1..1
kd1 PU Voltage controller derivative gain (<i>Kd1</i>). Typical value = 34,5. 1..1
tb1 Seconds Voltage controller derivative washout time constant (<i>Tb1</i>) (&gt;= 0). Typical value = 12,45. 1..1
pid1max PU Controller follow up gain (<i>PID1max</i>). Typical value = 2. 1..1
ti1 PU Controller follow up deadband (<i>Ti1</i>). Typical value = 0. 1..1
iefmax2 PU Minimum open circuit excitation voltage (<i>I</i><i><sub>efmax2</sub></i>). Typical value = -5. 1..1
k2 PU Gain (<i>K2</i>). Typical value = 5. 1..1
ketb PU Gain (<i>Ketb</i>). Typical value = 0,06. 1..1
upmax PU Limiter (<i>Upmax</i>) (&gt; ExcELIN2.upmin). Typical value = 3. 1..1
upmin PU Limiter (<i>Upmin</i>) (&lt; ExcELIN2.upmax). Typical value = 0. 1..1
te Seconds Time constant (<i>Te</i>) (&gt;= 0). Typical value = 0. 1..1
xp PU Excitation transformer effective reactance (<i>Xp</i>). Typical value = 1. 1..1
te2 Seconds Time Constant (<i>T</i><i><sub>e2</sub></i>) (&gt;= 0). Typical value = 1. 1..1
ke2 PU Gain (<i>Ke2</i>). Typical value = 0,1. 1..1
ve1 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>1</sub></i>) (&gt; 0). Typical value = 3. 1..1
seve1 PU Exciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>1</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>1</sub></i><i>]</i>) (&gt;= 0). Typical value = 0. 1..1
ve2 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>2</sub></i>) (&gt; 0). Typical value = 0. 1..1
seve2 PU Exciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>2</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>2</sub></i><i>]</i>) (&gt;= 0). Typical value = 1. 1..1
tr4 Seconds Time constant (<i>T</i><i><sub>r4</sub></i>) (&gt;= 0). Typical value = 1. 1..1
k3 PU Gain (<i>K3</i>). Typical value = 0,1. 1..1
ti3 Seconds Time constant (<i>T</i><i><sub>i3</sub></i>) (&gt;= 0). Typical value = 3. 1..1
k4 PU Gain (<i>K4</i>). Typical value = 0. 1..1
ti4 Seconds Time constant (<i>T</i><i><sub>i4</sub></i>) (&gt;= 0). Typical value = 0. 1..1
iefmax PU Limiter (<i>I</i><i><sub>efmax</sub></i>) (&gt; ExcELIN2.iefmin). Typical value = 1. 1..1
iefmin PU Limiter (<i>I</i><i><sub>efmin</sub></i>) (&lt; ExcELIN2.iefmax). Typical value = 1. 1..1
efdbas PU Gain (<i>Efdbas</i>). Typical value = 0,1. 1..1
Информация о классе
ID
cim:ExcELIN2
Тип
Class
Наследует
cim:ExcitationSystemDynamics
Свойств
27