ExcIEEEAC2A Class

IEEE 421.5-2005 type AC2A model. The model represents a high initial response field-controlled alternator-rectifier excitation system. The alternator main exciter is used with non-controlled rectifiers. The type AC2A model is similar to that of type AC1A except for the inclusion of exciter time constant compensation and exciter field current limiting elements. Reference: IEEE 421.5-2005, 6.2.

Diagram
Свойства (21)
ID Тип Описание Количество
tb Seconds Voltage regulator time constant (<i>T</i><i><sub>B</sub></i>) (&gt;= 0). Typical value = 0. 1..1
tc Seconds Voltage regulator time constant (<i>T</i><i><sub>C</sub></i>) (&gt;= 0). Typical value = 0. 1..1
ka PU Voltage regulator gain (<i>K</i><i><sub>A</sub></i>) (&gt; 0). Typical value = 400. 1..1
ta Seconds Voltage regulator time constant (<i>T</i><i><sub>A</sub></i>) (&gt; 0). Typical value = 0,02. 1..1
vamax PU Maximum voltage regulator output (<i>V</i><i><sub>AMAX</sub></i>) (&gt; 0). Typical value = 8. 1..1
vamin PU Minimum voltage regulator output (<i>V</i><i><sub>AMIN</sub></i>) (&lt; 0). Typical value = -8. 1..1
kb PU Second stage regulator gain (<i>K</i><i><sub>B</sub></i>) (&gt; 0). Typical value = 25. 1..1
vrmax PU Maximum voltage regulator outputs (<i>V</i><i><sub>RMAX</sub></i>) (&gt; 0). Typical value = 105. 1..1
vrmin PU Minimum voltage regulator outputs (<i>V</i><i><sub>RMIN</sub></i>) (&lt; 0). Typical value = -95. 1..1
te Seconds Exciter time constant, integration rate associated with exciter control (<i>T</i><i><sub>E</sub></i>) (&gt; 0). Typical value = 0,6. 1..1
vfemax PU Exciter field current limit reference (<i>V</i><i><sub>FEMAX</sub></i>) (&gt; 0). Typical value = 4,4. 1..1
kh PU Exciter field current feedback gain (<i>K</i><i><sub>H</sub></i>) (&gt;= 0). Typical value = 1. 1..1
kf PU Excitation control system stabilizer gains (<i>K</i><i><sub>F</sub></i>) (&gt;= 0). Typical value = 0,03. 1..1
tf Seconds Excitation control system stabilizer time constant (<i>T</i><i><sub>F</sub></i>) (&gt; 0). Typical value = 1. 1..1
kc PU Rectifier loading factor proportional to commutating reactance (<i>K</i><i><sub>C</sub></i>) (&gt;= 0). Typical value = 0,28. 1..1
kd PU Demagnetizing factor, a function of exciter alternator reactances (<i>K</i><i><sub>D</sub></i>) (&gt;= 0). Typical value = 0,35. 1..1
ke PU Exciter constant related to self-excited field (<i>K</i><i><sub>E</sub></i>) (&gt;= 0). Typical value = 1. 1..1
ve1 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>V</i><i><sub>E1</sub></i>) (&gt; 0). Typical value = 4,4. 1..1
seve1 Float Exciter saturation function value at the corresponding exciter voltage, <i>V</i><i><sub>E1</sub></i>, back of commutating reactance (<i>S</i><i><sub>E</sub></i><i>[V</i><i><sub>E1</sub></i><i>]</i>) (&gt;= 0). Typical value = 0,037. 1..1
ve2 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>V</i><i><sub>E2</sub></i>) (&gt; 0). Typical value = 3,3. 1..1
seve2 Float Exciter saturation function value at the corresponding exciter voltage, <i>V</i><i><sub>E2</sub></i>, back of commutating reactance (<i>S</i><i><sub>E</sub></i><i>[V</i><i><sub>E2</sub></i><i>]</i>) (&gt;= 0). Typical value = 0,012. 1..1
Информация о классе
ID
cim:ExcIEEEAC2A
Тип
Class
Наследует
cim:ExcitationSystemDynamics
Свойств
21