ExcIEEEAC4A Class

IEEE 421.5-2005 type AC4A model. The model represents type AC4A alternator-supplied controlled-rectifier excitation system which is quite different from the other types of AC systems. This high initial response excitation system utilizes a full thyristor bridge in the exciter output circuit. The voltage regulator controls the firing of the thyristor bridges. The exciter alternator uses an independent voltage regulator to control its output voltage to a constant value. These effects are not modelled; however, transient loading effects on the exciter alternator are included. Reference: IEEE 421.5-2005, 6.4.

Diagram
Свойства (9)
ID Тип Описание Количество
vimax PU Maximum voltage regulator input limit (<i>V</i><i><sub>IMAX</sub></i>) (&gt; 0). Typical value = 10. 1..1
vimin PU Minimum voltage regulator input limit (<i>V</i><i><sub>IMIN</sub></i>) (&lt; 0). Typical value = -10. 1..1
tc Seconds Voltage regulator time constant (<i>T</i><i><sub>C</sub></i>) (&gt;= 0). Typical value = 1. 1..1
tb Seconds Voltage regulator time constant (<i>T</i><i><sub>B</sub></i>) (&gt;= 0). Typical value = 10. 1..1
ka PU Voltage regulator gain (<i>K</i><i><sub>A</sub></i>) (&gt; 0). Typical value = 200. 1..1
ta Seconds Voltage regulator time constant (<i>T</i><i><sub>A</sub></i>) (&gt; 0). Typical value = 0,015. 1..1
vrmax PU Maximum voltage regulator output (<i>V</i><i><sub>RMAX</sub></i>) (&gt; 0). Typical value = 5,64. 1..1
vrmin PU Minimum voltage regulator output (<i>V</i><i><sub>RMIN</sub></i>) (&lt; 0). Typical value = -4,53. 1..1
kc PU Rectifier loading factor proportional to commutating reactance (<i>K</i><i><sub>C</sub></i>) (&gt;= 0). Typical value = 0. 1..1
Информация о классе
ID
cim:ExcIEEEAC4A
Тип
Class
Наследует
cim:ExcitationSystemDynamics
Свойств
9