ExcIEEEAC6A Class

IEEE 421.5-2005 type AC6A model. The model represents field-controlled alternator-rectifier excitation systems with system-supplied electronic voltage regulators. The maximum output of the regulator, <i>V</i><i><sub>R</sub></i>, is a function of terminal voltage, <i>V</i><i><sub>T</sub></i>. The field current limiter included in the original model AC6A remains in the 2005 update. Reference: IEEE 421.5-2005, 6.6.

Diagram
Свойства (22)
ID Тип Описание Количество
ka PU Voltage regulator gain (<i>K</i><i><sub>A</sub></i>) (&gt; 0). Typical value = 536. 1..1
ta Seconds Voltage regulator time constant (<i>T</i><i><sub>A</sub></i>) (&gt;= 0). Typical value = 0,086. 1..1
tk Seconds Voltage regulator time constant (<i>T</i><i><sub>K</sub></i>) (&gt;= 0). Typical value = 0,18. 1..1
tb Seconds Voltage regulator time constant (<i>T</i><i><sub>B</sub></i>) (&gt;= 0). Typical value = 9. 1..1
tc Seconds Voltage regulator time constant (<i>T</i><i><sub>C</sub></i>) (&gt;= 0). Typical value = 3. 1..1
vamax PU Maximum voltage regulator output (<i>V</i><i><sub>AMAX</sub></i>) (&gt; 0). Typical value = 75. 1..1
vamin PU Minimum voltage regulator output (V<sub>AMIN</sub>) (&lt; 0). Typical value = -75. 1..1
vrmax PU Maximum voltage regulator output (<i>V</i><i><sub>RMAX</sub></i>) (&gt; 0). Typical value = 44. 1..1
vrmin PU Minimum voltage regulator output (<i>V</i><i><sub>RMIN</sub></i>) (&lt; 0). Typical value = -36. 1..1
te Seconds Exciter time constant, integration rate associated with exciter control (<i>T</i><i><sub>E</sub></i>) (&gt; 0). Typical value = 1. 1..1
kh PU Exciter field current limiter gain (<i>K</i><i><sub>H</sub></i>) (&gt;= 0). Typical value = 92. 1..1
tj Seconds Exciter field current limiter time constant (<i>T</i><i><sub>J</sub></i>) (&gt;= 0). Typical value = 0,02. 1..1
th Seconds Exciter field current limiter time constant (<i>T</i><i><sub>H</sub></i>) (&gt; 0). Typical value = 0,08. 1..1
vfelim PU Exciter field current limit reference (<i>V</i><i><sub>FELIM</sub></i>) (&gt; 0). Typical value = 19. 1..1
vhmax PU Maximum field current limiter signal reference (<i>V</i><i><sub>HMAX</sub></i>) (&gt; 0). Typical value = 75. 1..1
kc PU Rectifier loading factor proportional to commutating reactance (<i>K</i><i><sub>C</sub></i>) (&gt;= 0). Typical value = 0,173. 1..1
kd PU Demagnetizing factor, a function of exciter alternator reactances (<i>K</i><i><sub>D</sub></i>) (&gt;= 0). Typical value = 1,91. 1..1
ke PU Exciter constant related to self-excited field (<i>K</i><i><sub>E</sub></i>). Typical value = 1,6. 1..1
ve1 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>V</i><i><sub>E1</sub></i>) (&gt; 0). Typical value = 7,4. 1..1
seve1 Float Exciter saturation function value at the corresponding exciter voltage, <i>V</i><i><sub>E1</sub></i>, back of commutating reactance (<i>S</i><i><sub>E</sub></i><i>[V</i><i><sub>E1</sub></i><i>])</i> (&gt;= 0). Typical value = 0,214. 1..1
ve2 PU Exciter alternator output voltages back of commutating reactance at which saturation is defined (<i>V</i><i><sub>E2</sub></i>) (&gt; 0). Typical value = 5,55. 1..1
seve2 Float Exciter saturation function value at the corresponding exciter voltage, <i>V</i><i><sub>E2</sub></i>, back of commutating reactance (<i>S</i><i><sub>E</sub></i><i>[V</i><i><sub>E2</sub></i><i>]</i>) (&gt;= 0). Typical value = 0,044. 1..1
Информация о классе
ID
cim:ExcIEEEAC6A
Тип
Class
Наследует
cim:ExcitationSystemDynamics
Свойств
22