ExcIEEEST5B Class

IEEE 421.5-2005 type ST5B model. The type ST5B excitation system is a variation of the type ST1A model, with alternative overexcitation and underexcitation inputs and additional limits. The block diagram in the IEEE 421.5 standard has input signal <i>Vc </i>and does not indicate the summation point with <i>Vref</i>. The implementation of the ExcIEEEST5B shall consider summation point with <i>Vref</i>. Reference: IEEE 421.5-2005, 7.5.

Diagram
Свойства (17)
ID Тип Описание Количество
kr PU Regulator gain (<i>K</i><i><sub>R</sub></i>) (&gt; 0). Typical value = 200. 1..1
t1 Seconds Firing circuit time constant (<i>T1</i>) (&gt;= 0). Typical value = 0,004. 1..1
kc PU Rectifier regulation factor (<i>K</i><i><sub>C</sub></i>) (&gt;= 0). Typical value = 0,004. 1..1
vrmax PU Maximum voltage regulator output (<i>V</i><i><sub>RMAX</sub></i>) (&gt; 0). Typical value = 5. 1..1
vrmin PU Minimum voltage regulator output (<i>V</i><i><sub>RMIN</sub></i>) (&lt; 0). Typical value = -4. 1..1
tc1 Seconds Regulator lead time constant (<i>T</i><i><sub>C1</sub></i>) (&gt;= 0). Typical value = 0,8. 1..1
tb1 Seconds Regulator lag time constant (<i>T</i><i><sub>B1</sub></i>) (&gt;= 0). Typical value = 6. 1..1
tc2 Seconds Regulator lead time constant (<i>T</i><i><sub>C2</sub></i>) (&gt;= 0). Typical value = 0,08. 1..1
tb2 Seconds Regulator lag time constant (<i>T</i><i><sub>B2</sub></i>) (&gt;= 0). Typical value = 0,01. 1..1
toc1 Seconds OEL lead time constant (<i>T</i><i><sub>OC1</sub></i>) (&gt;= 0). Typical value = 0,1. 1..1
tob1 Seconds OEL lag time constant (<i>T</i><i><sub>OB1</sub></i>) (&gt;= 0). Typical value = 2. 1..1
toc2 Seconds OEL lead time constant (<i>T</i><i><sub>OC2</sub></i>) (&gt;= 0). Typical value = 0,08. 1..1
tob2 Seconds OEL lag time constant (<i>T</i><i><sub>OB2</sub></i>) (&gt;= 0). Typical value = 0,08. 1..1
tuc1 Seconds UEL lead time constant (<i>T</i><i><sub>UC1</sub></i>) (&gt;= 0). Typical value = 2. 1..1
tub1 Seconds UEL lag time constant (<i>T</i><i><sub>UB1</sub></i>) (&gt;= 0). Typical value = 10. 1..1
tuc2 Seconds UEL lead time constant (<i>T</i><i><sub>UC2</sub></i>) (&gt;= 0). Typical value = 0,1. 1..1
tub2 Seconds UEL lag time constant (<i>T</i><i><sub>UB2</sub></i>) (&gt;= 0). Typical value = 0,05. 1..1
Информация о классе
ID
cim:ExcIEEEST5B
Тип
Class
Наследует
cim:ExcitationSystemDynamics
Свойств
17