GovSteamBB Class

European governor model.

Diagram
Свойства (17)
ID Тип Описание Количество
fcut PU Frequency deadband (<i>f</i><i><sub>cut</sub></i>) (&gt;= 0). Typical value = 0,002. 1..1
ks PU Gain (<i>Ks</i>). Typical value = 21,0. 1..1
kls PU Gain (<i>Kls</i>) (&gt; 0). Typical value = 0,1. 1..1
kg PU Gain (<i>Kg</i>). Typical value = 1,0. 1..1
t1 Seconds Time constant (<i>T1</i>). Typical value = 0,05. 1..1
kp PU Gain (<i>Kp</i>). Typical value = 1,0. 1..1
tn Seconds Time constant (<i>Tn</i>) (&gt; 0). Typical value = 1,0. 1..1
kd PU Gain (<i>Kd</i>). Typical value = 1,0. 1..1
td Seconds Time constant (<i>Td</i>) (&gt; 0). Typical value = 1,0. 1..1
pmax PU High power limit (<i>Pmax</i>) (&gt; GovSteamBB.pmin). Typical value = 1,0. 1..1
pmin PU Low power limit (<i>Pmin</i>) (&lt; GovSteamBB.pmax). Typical value = 0. 1..1
t4 Seconds Time constant (<i>T4</i>). Typical value = 0,15. 1..1
k2 PU Gain (<i>K2</i>). Typical value = 0,75. 1..1
t5 Seconds Time constant (<i>T5</i>). Typical value = 12,0. 1..1
k3 PU Gain (<i>K3</i>). Typical value = 0,5. 1..1
t6 Seconds Time constant (<i>T6</i>). Typical value = 0,75. 1..1
peflag Boolean Electric power input selection (Peflag). true = electric power input false = feedback signal. Typical value = false. 1..1
Информация о классе
ID
cim:GovSteamBB
Тип
Class
Наследует
cim:TurbineGovernorDynamics
Свойств
17