PssIEEE3B Class

IEEE 421.5-2005 type PSS3B power system stabilizer model. The PSS model PSS3B has dual inputs of electrical power and rotor angular frequency deviation. The signals are used to derive an equivalent mechanical power signal. This model has 2 input signals. They have the following fixed types (expressed in terms of InputSignalKind values): the first one is of rotorAngleFrequencyDeviation type and the second one is of generatorElectricalPower type. Reference: IEEE 3B 421.5-2005, 8.3.

Diagram
Свойства (17)
ID Тип Описание Количество
t1 Seconds Transducer time constant (<i>T1</i>) (&gt;= 0). Typical value = 0,012. 1..1
t2 Seconds Transducer time constant (<i>T2</i>) (&gt;= 0). Typical value = 0,012. 1..1
tw1 Seconds Washout time constant (<i>Tw1</i>) (&gt;= 0). Typical value = 0,3. 1..1
tw2 Seconds Washout time constant (<i>Tw2</i>) (&gt;= 0). Typical value = 0,3. 1..1
tw3 Seconds Washout time constant (<i>Tw3</i>) (&gt;= 0). Typical value = 0,6. 1..1
ks1 PU Gain on signal # 1 (<i>Ks1</i>). Typical value = -0,602. 1..1
ks2 PU Gain on signal # 2 (<i>Ks2</i>). Typical value = 30,12. 1..1
a1 PU Notch filter parameter (<i>A1</i>). Typical value = 0,359. 1..1
a2 PU Notch filter parameter (<i>A2</i>). Typical value = 0,586. 1..1
a3 PU Notch filter parameter (<i>A3</i>). Typical value = 0,429. 1..1
a4 PU Notch filter parameter (<i>A4</i>). Typical value = 0,564. 1..1
a5 PU Notch filter parameter (<i>A5</i>). Typical value = 0,001. 1..1
a6 PU Notch filter parameter (<i>A6</i>). Typical value = 0. 1..1
a7 PU Notch filter parameter (<i>A7</i>). Typical value = 0,031. 1..1
a8 PU Notch filter parameter (<i>A8</i>). Typical value = 0. 1..1
vstmax PU Stabilizer output maximum limit (<i>Vstmax</i>) (&gt; PssIEEE3B.vstmin). Typical value = 0,1. 1..1
vstmin PU Stabilizer output minimum limit (<i>Vstmin</i>) (&lt; PssIEEE3B.vstmax). Typical value = -0,1. 1..1
Информация о классе
ID
cim:PssIEEE3B
Тип
Class
Наследует
cim:PowerSystemStabilizerDynamics
Свойств
17