WindContPType3IEC Class

P control model type 3. Reference: IEC 61400-27-1:2015, 5.6.5.4.

Diagram
Свойства (25)
ID Тип Описание Количество
dpmax PU Maximum wind turbine power ramp rate (<i>dp</i><i><sub>max</sub></i>). It is a type-dependent parameter. 1..1
dprefmax PU Maximum ramp rate of wind turbine reference power (<i>dp</i><i><sub>refmax</sub></i>). It is a project-dependent parameter. 1..1
dprefmin PU Minimum ramp rate of wind turbine reference power (<i>dp</i><i><sub>refmin</sub></i>). It is a project-dependent parameter. 1..1
dthetamax PU Ramp limitation of torque, required in some grid codes (<i>dt</i><i><sub>max</sub></i>). It is a project-dependent parameter. 1..1
dthetamaxuvrt PU Limitation of torque rise rate during UVRT (<i>dtheta</i><i><sub>maxUVRT</sub></i>). It is a project-dependent parameter. 1..1
kdtd PU Gain for active drive train damping (<i>K</i><i><sub>DTD</sub></i>). It is a type-dependent parameter. 1..1
kip PU PI controller integration parameter (<i>K</i><sub>Ip</sub>). It is a type-dependent parameter. 1..1
kpp PU PI controller proportional gain (<i>K</i><sub>Pp</sub>). It is a type-dependent parameter. 1..1
mpuvrt Boolean Enable UVRT power control mode (<i>M</i><i><sub>pUVRT</sub></i><sub>)</sub>. It is a project-dependent parameter. true = voltage control (1 in the IEC model) false = reactive power control (0 in the IEC model). 1..1
omegaoffset PU Offset to reference value that limits controller action during rotor speed changes (<i>omega</i><i><sub>offset</sub></i>). It is a case-dependent parameter. 1..1
pdtdmax PU Maximum active drive train damping power (<i>p</i><sub>DTDmax</sub>). It is a type-dependent parameter. 1..1
tdvs Seconds Time<sub> </sub>delay after deep voltage sags (<i>T</i><i><sub>DVS</sub></i>) (&gt;= 0). It is a project-dependent parameter. 1..1
thetaemin PU Minimum electrical generator torque (<i>t</i><sub>emin</sub>). It is a type-dependent parameter. 1..1
thetauscale PU Voltage scaling factor of reset-torque (<i>t</i><sub>uscale</sub>). It is a project-dependent parameter. 1..1
tomegafiltp3 Seconds Filter time constant for generator speed measurement (<i>T</i><sub>omegafiltp3</sub>) (&gt;= 0). It is a type-dependent parameter. 1..1
tpfiltp3 Seconds Filter time constant for power measurement (<i>T</i><sub>pfiltp3</sub>) (&gt;= 0). It is a type-dependent parameter. 1..1
tpord PU Time constant in power order lag (<i>T</i><sub>pord</sub>). It is a type-dependent parameter. 1..1
tufiltp3 Seconds Filter time constant for voltage measurement (<i>T</i><sub>ufiltp3</sub>) (&gt;= 0). It is a type-dependent parameter. 1..1
tomegaref Seconds Time constant in speed reference filter (<i>T</i><sub>omega,ref</sub>) (&gt;= 0). It is a type-dependent parameter. 1..1
udvs PU Voltage limit for hold UVRT status after deep voltage sags (<i>u</i><i><sub>DVS</sub></i>). It is a project-dependent parameter. 1..1
updip PU Voltage dip threshold for P-control (<i>u</i><sub>Pdip</sub>). Part of turbine control, often different (e.g 0.8) from converter thresholds. It is a project-dependent parameter. 1..1
omegadtd PU Active drive train damping frequency (<i>omega</i><i><sub>DTD</sub></i>). It can be calculated from two mass model parameters. It is a type-dependent parameter. 1..1
zeta Float Coefficient for active drive train damping (<i>zeta</i>). It is a type-dependent parameter. 1..1
WindTurbineType3IEC WindTurbineType3IEC Wind turbine type 3 model with which this wind control P type 3 model is associated. 1
WindDynamicsLookupTable WindDynamicsLookupTable The wind dynamics lookup table associated with this P control type 3 model. 1..n
Ссылки (2)
Класс Свойство Описание
cim:WindTurbineType3IEC cim:WindContPType3IEC

Wind control P type 3 model associated with this wind turbine type 3 model.

cim:WindDynamicsLookupTable cim:WindContPType3IEC

The P control type 3 model with which this wind dynamics lookup table is associated.

Информация о классе
ID
cim:WindContPType3IEC
Тип
Class
Наследует
cim:IdentifiedObject
Свойств
25