WindContQIEC Class

Q control model. Reference: IEC 61400-27-1:2015, 5.6.5.7.

Diagram
Свойства (24)
ID Тип Описание Количество
iqh1 PU Maximum reactive current injection during dip (<i>i</i><i><sub>qh1</sub></i>). It is a type-dependent parameter. 1..1
iqmax PU Maximum reactive current injection (<i>i</i><i><sub>qmax</sub></i>) (&gt; WindContQIEC.iqmin). It is a type-dependent parameter. 1..1
iqmin PU Minimum reactive current injection (<i>i</i><i><sub>qmin</sub></i>) (&lt; WindContQIEC.iqmax). It is a type-dependent parameter. 1..1
iqpost PU Post fault reactive current injection (<i>i</i><i><sub>qpost</sub></i>). It is a project-dependent parameter. 1..1
kiq PU Reactive power PI controller integration gain (<i>K</i><i><sub>I,q</sub></i>). It is a type-dependent parameter. 1..1
kiu PU Voltage PI controller integration gain (<i>K</i><i><sub>I,u</sub></i>). It is a type-dependent parameter. 1..1
kpq PU Reactive power PI controller proportional gain (<i>K</i><i><sub>P,q</sub></i>). It is a type-dependent parameter. 1..1
kpu PU Voltage PI controller proportional gain (<i>K</i><i><sub>P,u</sub></i>). It is a type-dependent parameter. 1..1
kqv PU Voltage scaling factor for UVRT current (<i>K</i><i><sub>qv</sub></i>). It is a project-dependent parameter. 1..1
tpfiltq Seconds Power measurement filter time constant (<i>T</i><i><sub>pfiltq</sub></i>) (&gt;= 0). It is a type-dependent parameter. 1..1
rdroop PU Resistive component of voltage drop impedance (<i>r</i><i><sub>droop</sub></i>) (&gt;= 0). It is a project-dependent parameter. 1..1
tufiltq Seconds Voltage measurement filter time constant (<i>T</i><i><sub>ufiltq</sub></i>) (&gt;= 0). It is a type-dependent parameter. 1..1
tpost Seconds Length of time period where post fault reactive power is injected (<i>T</i><i><sub>post</sub></i>) (&gt;= 0). It is a project-dependent parameter. 1..1
tqord Seconds Time constant in reactive power order lag (<i>T</i><i><sub>qord</sub></i>) (&gt;= 0). It is a type-dependent parameter. 1..1
udb1 PU Voltage deadband lower limit (<i>u</i><i><sub>db1</sub></i>). It is a type-dependent parameter. 1..1
udb2 PU Voltage deadband upper limit (<i>u</i><i><sub>db2</sub></i>). It is a type-dependent parameter. 1..1
umax PU Maximum voltage in voltage PI controller integral term (<i>u</i><i><sub>max</sub></i>) (&gt; WindContQIEC.umin). It is a type-dependent parameter. 1..1
umin PU Minimum voltage in voltage PI controller integral term (<i>u</i><i><sub>min</sub></i>) (&lt; WindContQIEC.umax). It is a type-dependent parameter. 1..1
uqdip PU Voltage threshold for UVRT detection in Q control (<i>u</i><i><sub>qdip</sub></i>). It is a type-dependent parameter. 1..1
uref0 PU User-defined bias in voltage reference (<i>u</i><i><sub>ref0</sub></i>). It is a case-dependent parameter. 1..1
windQcontrolModesType WindQcontrolModeKind Types of general wind turbine Q control modes (<i>M</i><i><sub>qG</sub></i>). It is a project-dependent parameter. 1..1
windUVRTQcontrolModesType WindUVRTQcontrolModeKind Types of UVRT Q control modes (<i>M</i><i><sub>qUVRT</sub></i>). It is a project-dependent parameter. 1..1
xdroop PU Inductive component of voltage drop impedance (<i>x</i><i><sub>droop</sub></i>) (&gt;= 0). It is a project-dependent parameter. 1..1
WindTurbineType3or4IEC WindTurbineType3or4IEC Wind turbine type 3 or type 4 model with which this reactive control model is associated. 1
Ссылки (1)
Класс Свойство Описание
cim:WindTurbineType3or4IEC cim:WIndContQIEC

Wind control Q model associated with this wind turbine type 3 or type 4 model.

Информация о классе
ID
cim:WindContQIEC
Тип
Class
Наследует
cim:IdentifiedObject
Свойств
24