WindPlantFreqPcontrolIEC Class

Frequency and active power controller model. Reference: IEC 61400-27-1:2015, Annex D.

Diagram
Свойства (17)
ID Тип Описание Количество
WindDynamicsLookupTable WindDynamicsLookupTable The wind dynamics lookup table associated with this frequency and active power wind plant model. 1..n
dprefmax PU Maximum ramp rate of <i>p</i><i><sub>WTref</sub></i> request from the plant controller to the wind turbines (<i>dp</i><i><sub>refmax</sub></i>) (&gt; WindPlantFreqPcontrolIEC.dprefmin). It is a case-dependent parameter. 1..1
dprefmin PU Minimum (negative) ramp rate of <i>p</i><i><sub>WTref</sub></i> request from the plant controller to the wind turbines (<i>dp</i><i><sub>refmin</sub></i>) (&lt; WindPlantFreqPcontrolIEC.dprefmax). It is a project-dependent parameter. 1..1
dpwprefmax PU Maximum positive ramp rate for wind plant power reference (<i>dp</i><i><sub>WPrefmax</sub></i>) (&gt; WindPlantFreqPcontrolIEC.dpwprefmin). It is a project-dependent parameter. 1..1
dpwprefmin PU Maximum negative ramp rate for wind plant power reference (<i>dp</i><i><sub>WPrefmin</sub></i>) (&lt; WindPlantFreqPcontrolIEC.dpwprefmax). It is a project-dependent parameter. 1..1
prefmax PU Maximum <i>p</i><i><sub>WTref</sub></i> request from the plant controller to the wind turbines (<i>p</i><i><sub>refmax</sub></i>) (&gt; WindPlantFreqPcontrolIEC.prefmin). It is a project-dependent parameter. 1..1
prefmin PU Minimum <i>p</i><i><sub>WTref</sub></i> request from the plant controller to the wind turbines (<i>p</i><i><sub>refmin</sub></i>) (&lt; WindPlantFreqPcontrolIEC.prefmax). It is a project-dependent parameter. 1..1
kiwpp Float Plant P controller integral gain (<i>K</i><i><sub>IWPp</sub></i>). It is a project-dependent parameter. 1..1
kiwppmax PU Maximum PI integrator term (<i>K</i><i><sub>IWPpmax</sub></i>) (&gt; WindPlantFreqPcontrolIEC.kiwppmin). It is a project-dependent parameter. 1..1
kiwppmin PU Minimum PI integrator term (<i>K</i><i><sub>IWPpmin</sub></i>) (&lt; WindPlantFreqPcontrolIEC.kiwppmax). It is a project-dependent parameter. 1..1
kpwpp Float Plant P controller proportional gain (<i>K</i><i><sub>PWPp</sub></i>). It is a project-dependent parameter. 1..1
kwppref PU Power reference gain (<i>K</i><i><sub>WPpref</sub></i>). It is a project-dependent parameter. 1..1
tpft Seconds Lead time constant in reference value transfer function (<i>T</i><i><sub>pft</sub></i>) (&gt;= 0). It is a project-dependent parameter. 1..1
tpfv Seconds Lag time constant in reference value transfer function (<i>T</i><i><sub>pfv</sub></i>) (&gt;= 0). It is a project-dependent parameter. 1..1
twpffiltp Seconds Filter time constant for frequency measurement (<i>T</i><i><sub>WPffiltp</sub></i>) (&gt;= 0). It is a project-dependent parameter. 1..1
twppfiltp Seconds Filter time constant for active power measurement (<i>T</i><i><sub>WPpfiltp</sub></i>) (&gt;= 0). It is a project-dependent parameter. 1..1
WindPlantIEC WindPlantIEC Wind plant model with which this wind plant frequency and active power control is associated. 1
Ссылки (2)
Класс Свойство Описание
cim:WindDynamicsLookupTable cim:WindPlantFreqPcontrolIEC

The frequency and active power wind plant control model with which this wind dynamics lookup table is associated.

cim:WindPlantIEC cim:WindPlantFreqPcontrolIEC

Wind plant frequency and active power control model associated with this wind plant.

Информация о классе
ID
cim:WindPlantFreqPcontrolIEC
Тип
Class
Наследует
cim:IdentifiedObject
Свойств
17