WindPlantReactiveControlIEC Class
Simplified plant voltage and reactive power control model for use with type 3 and type 4 wind turbine models. Reference: IEC 61400-27-1:2015, Annex D.
Diagram
Свойства (20)
| ID | Тип | Описание | Количество |
|---|---|---|---|
| WindDynamicsLookupTable | WindDynamicsLookupTable | The wind dynamics lookup table associated with this voltage and reactive power wind plant model. | 1..n |
| WindPlantIEC | WindPlantIEC | Wind plant reactive control model associated with this wind plant. | 1 |
| dxrefmax | PU | Maximum positive ramp rate for wind turbine reactive power/voltage reference (<i>dx</i><i><sub>refmax</sub></i>) (> WindPlantReactiveControlIEC.dxrefmin). It is a project-dependent parameter. | 1..1 |
| dxrefmin | PU | Maximum negative ramp rate for wind turbine reactive power/voltage reference (<i>dx</i><i><sub>refmin</sub></i>) (< WindPlantReactiveControlIEC.dxrefmax). It is a project-dependent parameter. | 1..1 |
| kiwpx | Float | Plant Q controller integral gain (<i>K</i><i><sub>IWPx</sub></i>). It is a project-dependent parameter. | 1..1 |
| kiwpxmax | PU | Maximum reactive power/voltage reference from integration (<i>K</i><i><sub>IWPxmax</sub></i>) (> WindPlantReactiveControlIEC.kiwpxmin). It is a project-dependent parameter. | 1..1 |
| kiwpxmin | PU | Minimum reactive power/voltage reference from integration (<i>K</i><i><sub>IWPxmin</sub></i>) (< WindPlantReactiveControlIEC.kiwpxmax). It is a project-dependent parameter. | 1..1 |
| kpwpx | Float | Plant Q controller proportional gain (<i>K</i><i><sub>PWPx</sub></i>). It is a project-dependent parameter. | 1..1 |
| kwpqref | PU | Reactive power reference gain (<i>K</i><i><sub>WPqref</sub></i>). It is a project-dependent parameter. | 1..1 |
| kwpqu | PU | Plant voltage control droop (<i>K</i><i><sub>WPqu</sub></i>). It is a project-dependent parameter. | 1..1 |
| tuqfilt | Seconds | Filter time constant for voltage-dependent reactive power (<i>T</i><i><sub>uqfilt</sub></i>) (>= 0). It is a project-dependent parameter. | 1..1 |
| twppfiltq | Seconds | Filter time constant for active power measurement (<i>T</i><i><sub>WPpfiltq</sub></i>) (>= 0). It is a project-dependent parameter. | 1..1 |
| twpqfiltq | Seconds | Filter time constant for reactive power measurement (<i>T</i><i><sub>WPqfiltq</sub></i>) (>= 0). It is a project-dependent parameter. | 1..1 |
| twpufiltq | Seconds | Filter time constant for voltage measurement (<i>T</i><i><sub>WPufiltq</sub></i>) (>= 0). It is a project-dependent parameter. | 1..1 |
| txft | Seconds | Lead time constant in reference value transfer function (<i>T</i><i><sub>xft</sub></i>) (>= 0). It is a project-dependent parameter. | 1..1 |
| txfv | Seconds | Lag time constant in reference value transfer function (<i>T</i><i><sub>xfv</sub></i>) (>= 0). It is a project-dependent parameter. | 1..1 |
| uwpqdip | PU | Voltage threshold for UVRT detection in Q control (<i>u</i><i><sub>WPqdip</sub></i>). It is a project-dependent parameter. | 1..1 |
| windPlantQcontrolModesType | WindPlantQcontrolModeKind | Reactive power/voltage controller mode (<i>M</i><i><sub>WPqmode</sub></i>). It is a case-dependent parameter. | 1..1 |
| xrefmax | PU | Maximum <i>x</i><sub>WTref</sub> (<i>q</i><i><sub>WTref</sub></i> or delta<i> u</i><i><sub>WTref</sub></i>) request from the plant controller (<i>x</i><i><sub>refmax</sub></i>) (> WindPlantReactiveControlIEC.xrefmin). It is a case-dependent parameter. | 1..1 |
| xrefmin | PU | Minimum <i>x</i><i><sub>WTref</sub></i> (<i>q</i><i><sub>WTref</sub></i> or delta <i>u</i><i><sub>WTref</sub></i>) request from the plant controller (<i>x</i><i><sub>refmin</sub></i>) (< WindPlantReactiveControlIEC.xrefmax). It is a project-dependent parameter. | 1..1 |
Ссылки (2)
| Класс | Свойство | Описание |
|---|---|---|
| cim:WindDynamicsLookupTable | cim:WindPlantReactiveControlIEC |
The voltage and reactive power wind plant control model with which this wind dynamics lookup table is associated. |
| cim:WindPlantIEC | cim:WindPlantReactiveControlIEC |
Wind plant model with which this wind reactive control is associated. |
Информация о классе
- ID
cim:WindPlantReactiveControlIEC- Тип
- Class
- Наследует
- cim:IdentifiedObject
- Свойств
- 20