TapChangerTablePoint.b

The magnetizing branch susceptance deviation as a percentage of nominal value. The actual susceptance is calculated as follows: calculated magnetizing susceptance = b(nominal) * (1 + b(from this class)/100). The b(nominal) is defined as the static magnetizing susceptance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.

Информация о свойстве
ID
TapChangerTablePoint.b
Класс
cim:TapChangerTablePoint Describes each tap step in the tabular curve.
Тип
PerCent Percentage on a defined base. For example, specify as 100 to indicate at the defined base.
Количество
0..1