PerCent Data Type
Percentage on a defined base. For example, specify as 100 to indicate at the defined base.
Ссылки (15)
| Класс | Свойство | Описание |
|---|---|---|
| cim:AsynchronousMachine | cim:efficiency |
Efficiency of the asynchronous machine at nominal operation as a percentage. Indicator for converter drive motors. Used for short circuit data exchange according to IEC 60909. |
| cim:SynchronousMachine | cim:voltageRegulationRange |
Range of generator voltage regulation (PG in IEC 60909-0) used for calculation of the impedance correction factor KG defined in IEC 60909-0. This attribute is used to describe the operating voltage of the generating unit. |
| cim:SynchronousMachine | cim:qPercent |
Part of the coordinated reactive control that comes from this machine. The attribute is used as a participation factor not necessarily summing up to 100% for the participating devices in the control. |
| cim:VsConverter | cim:qShare |
Reactive power sharing factor among parallel converters on Uac control. The attribute shall be a positive value or zero. |
| cim:EnergyConsumer | cim:pfixedPct |
Fixed active power as a percentage of load group fixed active power. Used to represent the time-varying components. Load sign convention is used, i.e. positive sign means flow out from a node. |
| cim:EnergyConsumer | cim:qfixedPct |
Fixed reactive power as a percentage of load group fixed reactive power. Used to represent the time-varying components. Load sign convention is used, i.e. positive sign means flow out from a node. |
| cim:GeneratingUnit | cim:governorSCD |
Governor Speed Changer Droop. This is the change in generator power output divided by the change in frequency normalized by the nominal power of the generator and the nominal frequency and expressed in percent and negated. A positive value of speed change droop provides additional generator output upon a drop in frequency. |
| cim:GeneratingUnit | cim:totalEfficiency |
The efficiency of the unit in converting the fuel into electrical energy. |
| cim:PhaseTapChangerNonLinear | cim:voltageStepIncrement |
The voltage step increment on the out of phase winding (the PowerTransformerEnd where the TapChanger is located) specified in percent of rated voltage of the PowerTransformerEnd. A positive value means a positive voltage variation from the Terminal at the PowerTransformerEnd, where the TapChanger is located, into the transformer. When the increment is negative, the voltage decreases when the tap step increases. |
| cim:TapChangerTablePoint | cim:b |
The magnetizing branch susceptance deviation as a percentage of nominal value. The actual susceptance is calculated as follows: calculated magnetizing susceptance = b(nominal) * (1 + b(from this class)/100). The b(nominal) is defined as the static magnetizing susceptance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form. |
| cim:TapChangerTablePoint | cim:g |
The magnetizing branch conductance deviation as a percentage of nominal value. The actual conductance is calculated as follows: calculated magnetizing conductance = g(nominal) * (1 + g(from this class)/100). The g(nominal) is defined as the static magnetizing conductance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form. |
| cim:TapChangerTablePoint | cim:r |
The resistance deviation as a percentage of nominal value. The actual reactance is calculated as follows: calculated resistance = r(nominal) * (1 + r(from this class)/100). The r(nominal) is defined as the static resistance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form. |
| cim:TapChangerTablePoint | cim:x |
The series reactance deviation as a percentage of nominal value. The actual reactance is calculated as follows: calculated reactance = x(nominal) * (1 + x(from this class)/100). The x(nominal) is defined as the static series reactance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form. |
| cim:RatioTapChanger | cim:stepVoltageIncrement |
Tap step increment, in per cent of rated voltage of the power transformer end, per step position. When the increment is negative, the voltage decreases when the tap step increases. |
| cim:MeasurementValue | cim:sensorAccuracy |
The limit, expressed as a percentage of the sensor maximum, that errors will not exceed when the sensor is used under reference conditions. |