TapChangerTablePoint.g

The magnetizing branch conductance deviation as a percentage of nominal value. The actual conductance is calculated as follows: calculated magnetizing conductance = g(nominal) * (1 + g(from this class)/100). The g(nominal) is defined as the static magnetizing conductance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.

Информация о свойстве
ID
TapChangerTablePoint.g
Класс
cim:TapChangerTablePoint Describes each tap step in the tabular curve.
Тип
PerCent Percentage on a defined base. For example, specify as 100 to indicate at the defined base.
Количество