Basic hydro turbine governor.

Diagram
Свойства (14)
ID Тип Описание Количество
mwbase ActivePower Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW. 1..1
rperm PU Permanent droop (<i>R</i>) (&gt; 0). Typical value = 0,04. 1..1
rtemp PU Temporary droop (<i>r</i>) (&gt; GovHydro1.rperm). Typical value = 0,3. 1..1
tr Seconds Washout time constant (<i>Tr</i>) (&gt; 0). Typical value = 5. 1..1
tf Seconds Filter time constant (<i>Tf</i>) (&gt; 0). Typical value = 0,05. 1..1
tg Seconds Gate servo time constant (<i>Tg</i>) (&gt; 0). Typical value = 0,5. 1..1
velm Float Maximum gate velocity (<i>Vlem</i>) (&gt; 0). Typical value = 0,2. 1..1
gmax PU Maximum gate opening (<i>Gmax</i>) (&gt; 0 and &gt; GovHydro.gmin). Typical value = 1. 1..1
gmin PU Minimum gate opening (<i>Gmin</i>) (&gt;= 0 and &lt; GovHydro1.gmax). Typical value = 0. 1..1
tw Seconds Water inertia time constant (<i>Tw</i>) (&gt; 0). Typical value = 1. 1..1
at PU Turbine gain (<i>At</i>) (&gt; 0). Typical value = 1,2. 1..1
dturb PU Turbine damping factor (<i>Dturb</i>) (&gt;= 0). Typical value = 0,5. 1..1
qnl PU No-load flow at nominal head (<i>qnl</i>) (&gt;= 0). Typical value = 0,08. 1..1
hdam PU Turbine nominal head (<i>hdam</i>). Typical value = 1. 1..1