ActivePower Data Type

Product of RMS value of the voltage and the RMS value of the in-phase component of the current.

Ссылки (73)
Класс Свойство Описание
cim:AsynchronousMachine cim:ratedMechanicalPower

Rated mechanical power (Pr in IEC 60909-0). Used for short circuit data exchange according to IEC 60909.

cim:RotatingMachine cim:p

Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution.

cim:EnergySource cim:pMin

This is the minimum active power that can be produced by the source. Load sign convention is used, i.e. positive sign means flow out from a TopologicalNode (bus) into the conducting equipment.

cim:EnergySource cim:pMax

This is the maximum active power that can be produced by the source. Load sign convention is used, i.e. positive sign means flow out from a TopologicalNode (bus) into the conducting equipment.

cim:EnergySource cim:activePower

High voltage source active injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions.

cim:EquivalentInjection cim:maxP

Maximum active power of the injection.

cim:EquivalentInjection cim:minP

Minimum active power of the injection.

cim:EquivalentInjection cim:p

Equivalent active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions.

cim:ExternalNetworkInjection cim:maxP

Maximum active power of the injection.

cim:ExternalNetworkInjection cim:minP

Minimum active power of the injection.

cim:ExternalNetworkInjection cim:p

Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions.

cim:ACDCConverter cim:poleLossP

The active power loss at a DC Pole = idleLoss + switchingLoss*|Idc| + resitiveLoss*Idc^2. For lossless operation Pdc=Pac. For rectifier operation with losses Pdc=Pac-lossP. For inverter operation with losses Pdc=Pac+lossP. It is converter’s state variable used in power flow. The attribute shall be a positive value.

cim:ACDCConverter cim:idleLoss

Active power loss in pole at no power transfer. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

cim:ACDCConverter cim:maxP

Maximum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.

cim:ACDCConverter cim:minP

Minimum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.

cim:ACDCConverter cim:p

Active power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution in the case a simplified power flow model is used.

cim:ACDCConverter cim:targetPpcc

Real power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.

cim:SvInjection cim:pInjection

The active power mismatch between calculated injection and initial injection. Positive sign means injection into the TopologicalNode (bus).

cim:SvPowerFlow cim:p

The active power flow. Load sign convention is used, i.e. positive sign means flow out from a TopologicalNode (bus) into the conducting equipment.

cim:EnergyConsumer cim:pfixed

Active power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used, i.e. positive sign means flow out from a node.

cim:EnergyConsumer cim:p

Active power of the load. Load sign convention is used, i.e. positive sign means flow out from a node. For voltage dependent loads the value is at rated voltage. Starting value for a steady state solution.

cim:PowerElectronicsConnection cim:p

Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution.

cim:GovHydroIEEE0 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovHydroIEEE2 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovSteamIEEE1 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0)<i>. </i>Unit = MW.

cim:GovCT1 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovCT2 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovGAST cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovGAST1 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovGAST1 cim:db2

Unintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0.

cim:GovGAST2 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovGAST2 cim:trate

Turbine rating (<i>Trate</i>). Unit = MW.

cim:GovGASTWD cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovGASTWD cim:trate

Turbine rating (<i>Trate</i>). Unit = MW.

cim:GovHydro1 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovHydro2 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovHydro2 cim:db2

Unintentional deadband (<i>db2</i>). Unit = MW. Typical value = 0.

cim:GovHydro3 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovHydro3 cim:db2

Unintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0.

cim:GovHydro4 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovHydro4 cim:db2

Unintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0.

cim:GovHydroDD cim:mwbase

Base for power values (<i>MWbase</i>) (&gt;0). Unit = MW.

cim:GovHydroDD cim:db2

Unintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0.

cim:GovHydroPID cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovHydroPID cim:db2

Unintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0.

cim:GovHydroPID2 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt;0). Unit = MW.

cim:GovHydroR cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovHydroR cim:db2

Unintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0.

cim:GovHydroWEH cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovHydroWPID cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovSteam0 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovSteam1 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovSteam1 cim:db2

Unintentional deadband (<i>db2</i>). Unit = MW. Typical value = 0.

cim:GovSteamCC cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovSteamEU cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovSteamFV2 cim:mwbase

Alternate base used instead of machine base in equipment model if necessary (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovSteamFV3 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:GovSteamSGO cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:TurbLCFB1 cim:mwbase

Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW.

cim:TurbLCFB1 cim:pmwset

Power controller setpoint (<i>Pmwset</i>) (see parameter detail 1). Unit = MW. Typical value = 0.

cim:ActivePowerLimit cim:normalValue

The normal value of active power limit. The attribute shall be a positive value or zero.

cim:ActivePowerLimit cim:value

Value of active power limit. The attribute shall be a positive value or zero.

cim:PowerElectronicsUnit cim:maxP

Maximum active power limit. This is the maximum (nameplate) limit for the unit.

cim:PowerElectronicsUnit cim:minP

Minimum active power limit. This is the minimum (nameplate) limit for the unit.

cim:ControlArea cim:netInterchange

The specified positive net interchange into the control area, i.e. positive sign means flow into the area.

cim:ControlArea cim:pTolerance

Active power net interchange tolerance. The attribute shall be a positive value or zero.

cim:GeneratingUnit cim:maximumAllowableSpinningReserve

Maximum allowable spinning reserve. Spinning reserve will never be considered greater than this value regardless of the current operating point.

cim:GeneratingUnit cim:maxOperatingP

This is the maximum operating active power limit the dispatcher can enter for this unit.

cim:GeneratingUnit cim:minOperatingP

This is the minimum operating active power limit the dispatcher can enter for this unit.

cim:GeneratingUnit cim:nominalP

The nominal power of the generating unit. Used to give precise meaning to percentage based attributes such as the governor speed change droop (governorSCD attribute). The attribute shall be a positive value equal to or less than RotatingMachine.ratedS.

cim:GeneratingUnit cim:ratedGrossMaxP

The unit's gross rated maximum capacity (book value). The attribute shall be a positive value.

cim:GeneratingUnit cim:ratedGrossMinP

The gross rated minimum generation level which the unit can safely operate at while delivering power to the transmission grid. The attribute shall be a positive value.

cim:GeneratingUnit cim:ratedNetMaxP

The net rated maximum capacity determined by subtracting the auxiliary power used to operate the internal plant machinery from the rated gross maximum capacity. The attribute shall be a positive value.