GovHydroIEEE0 Class

IEEE simplified hydro governor-turbine model. Used for mechanical-hydraulic and electro-hydraulic turbine governors, with or without steam feedback. Typical values given are for mechanical-hydraulic turbine-governor. Ref<font color="#0f0f0f">erence: IEEE Transactions on Power Apparatus and Systems, November/December 1973, Volume PAS-92, Number 6, <i><u>Dynamic Models for Steam and Hydro Turbines in Power System Studies</u></i>, page 1904.</font>

Diagram
Свойства (8)
ID Тип Описание Количество
mwbase ActivePower Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW. 1..1
k PU Governor gain (<i>K)</i>. 1..1
t1 Seconds Governor lag time constant (<i>T1</i>) (&gt;= 0). Typical value = 0,25. 1..1
t2 Seconds Governor lead time constant (<i>T2)</i> (&gt;= 0). Typical value = 0. 1..1
t3 Seconds Gate actuator time constant (<i>T3</i>) (&gt;= 0). Typical value = 0,1. 1..1
t4 Seconds Water starting time (<i>T4</i>) (&gt;= 0). 1..1
pmax PU Gate maximum (<i>Pmax</i>) (&gt; GovHydroIEEE0.pmin). 1..1
pmin PU Gate minimum (<i>Pmin</i>) (&lt; GovHydroIEEE.pmax). 1..1
Информация о классе
ID
cim:GovHydroIEEE0
Тип
Class
Наследует
cim:TurbineGovernorDynamics
Свойств
8