GovHydroIEEE2 Class
IEEE hydro turbine governor model represents plants with straightforward penstock configurations and hydraulic-dashpot governors. Ref<font color="#0f0f0f">erence: IEEE Transactions on Power Apparatus and Systems, November/December 1973, Volume PAS-92, Number 6, <i><u>Dynamic Models for Steam and Hydro Turbines in Power System Studies</u></i>, page 1904.</font>
Diagram
Свойства (26)
| ID | Тип | Описание | Количество |
|---|---|---|---|
| mwbase | ActivePower | Base for power values (<i>MWbase</i>) (> 0). Unit = MW. | 1..1 |
| tg | Seconds | Gate servo time constant (<i>Tg</i>) (>= 0). Typical value = 0,5. | 1..1 |
| tp | Seconds | Pilot servo valve time constant (<i>Tp</i>) (>= 0). Typical value = 0,03. | 1..1 |
| uo | Float | Maximum gate opening velocity (<i>Uo</i>). Unit = PU / s. Typical value = 0,1. | 1..1 |
| uc | Float | Maximum gate closing velocity (<i>Uc</i>) (<0). Typical value = -0,1. | 1..1 |
| pmax | PU | Maximum gate opening (<i>Pmax</i>) (> GovHydroIEEE2.pmin). Typical value = 1. | 1..1 |
| pmin | PU | Minimum gate opening (<i>Pmin</i>) (<GovHydroIEEE2.pmax). Typical value = 0. | 1..1 |
| rperm | PU | Permanent droop (<i>Rperm</i>). Typical value = 0,05. | 1..1 |
| rtemp | PU | Temporary droop (<i>Rtemp</i>). Typical value = 0,5. | 1..1 |
| tr | Seconds | Dashpot time constant (<i>Tr</i>) (>= 0). Typical value = 12. | 1..1 |
| tw | Seconds | Water inertia time constant (<i>Tw</i>) (>= 0). Typical value = 2. | 1..1 |
| kturb | PU | Turbine gain (<i>Kturb</i>). Typical value = 1. | 1..1 |
| aturb | PU | Turbine numerator multiplier (<i>Aturb</i>). Typical value = -1. | 1..1 |
| bturb | PU | Turbine denominator multiplier (<i>Bturb</i>) (> 0). Typical value = 0,5. | 1..1 |
| gv1 | PU | Nonlinear gain point 1, PU gv (<i>Gv1</i>). Typical value = 0. | 1..1 |
| pgv1 | PU | Nonlinear gain point 1, PU power (<i>Pgv1</i>). Typical value = 0. | 1..1 |
| gv2 | PU | Nonlinear gain point 2, PU gv (<i>Gv2</i>). Typical value = 0. | 1..1 |
| pgv2 | PU | Nonlinear gain point 2, PU power (<i>Pgv2</i>). Typical value = 0. | 1..1 |
| gv3 | PU | Nonlinear gain point 3, PU gv (<i>Gv3</i>). Typical value = 0. | 1..1 |
| pgv3 | PU | Nonlinear gain point 3, PU power (<i>Pgv3</i>). Typical value = 0. | 1..1 |
| gv4 | PU | Nonlinear gain point 4, PU gv (<i>Gv4</i>). Typical value = 0. | 1..1 |
| pgv4 | PU | Nonlinear gain point 4, PU power (<i>Pgv4</i>). Typical value = 0. | 1..1 |
| gv5 | PU | Nonlinear gain point 5, PU gv (<i>Gv5</i>). Typical value = 0. | 1..1 |
| pgv5 | PU | Nonlinear gain point 5, PU power (<i>Pgv5</i>). Typical value = 0. | 1..1 |
| gv6 | PU | Nonlinear gain point 6, PU gv (<i>Gv6</i>). Typical value = 0. | 1..1 |
| pgv6 | PU | Nonlinear gain point 6, PU power (<i>Pgv6</i>). Typical value = 0. | 1..1 |
Информация о классе
- ID
cim:GovHydroIEEE2- Тип
- Class
- Наследует
- cim:TurbineGovernorDynamics
- Свойств
- 26