GovHydroPID2 Class

Hydro turbine and governor. Represents plants with straightforward penstock configurations and "three term" electro-hydraulic governors (i.e. Woodward<sup>TM</sup> electronic). [Footnote: Woodward electronic governors are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]

Diagram
Свойства (22)
ID Тип Описание Количество
mwbase ActivePower Base for power values (<i>MWbase</i>) (&gt;0). Unit = MW. 1..1
treg Seconds Speed detector time constant (<i>Treg</i>) (&gt;= 0). Typical value = 0. 1..1
rperm PU Permanent drop (<i>Rperm</i>). Typical value = 0. 1..1
kp PU Proportional gain (<i>Kp</i>). Typical value = 0. 1..1
ki Float Reset gain (<i>Ki</i>). Unit = PU/s. Typical value = 0. 1..1
kd PU Derivative gain (<i>Kd</i>). Typical value = 0. 1..1
ta Seconds Controller time constant (<i>Ta</i>) (&gt;= 0). Typical value = 0. 1..1
tb Seconds Gate servo time constant (<i>Tb</i>) (&gt; 0). 1..1
velmax Float Maximum gate opening velocity (<i>Velmax</i>) (&lt; GovHydroPID2.velmin). Unit = PU / s. Typical value = 0. 1..1
velmin Float Maximum gate closing velocity (<i>Velmin</i>) (&gt; GovHydroPID2.velmax). Unit = PU / s. Typical value = 0. 1..1
gmax PU Maximum gate opening (<i>Gmax</i>) (&gt; GovHydroPID2.gmin). Typical value = 0. 1..1
gmin PU Minimum gate opening (<i>Gmin</i>) (&gt; GovHydroPID2.gmax). Typical value = 0. 1..1
tw Seconds Water inertia time constant (<i>Tw</i>) (&gt;= 0). Typical value = 0. 1..1
d PU Turbine damping factor (<i>D</i>). Unit = delta P / delta speed. Typical value = 0. 1..1
g0 PU Gate opening at speed no load (<i>G0</i>). Typical value = 0. 1..1
g1 PU Intermediate gate opening (<i>G1</i>). Typical value = 0. 1..1
p1 PU Power at gate opening <i>G1</i> (<i>P1</i>). Typical value = 0. 1..1
g2 PU Intermediate gate opening (<i>G2</i>). Typical value = 0. 1..1
p2 PU Power at gate opening G2 (<i>P2</i>). Typical value = 0. 1..1
p3 PU Power at full opened gate (<i>P3</i>). Typical value = 0. 1..1
atw PU Factor multiplying <i>Tw</i> (<i>Atw</i>). Typical value = 0. 1..1
feedbackSignal Boolean Feedback signal type flag (<i>Flag</i>). true = use gate position feedback signal false = use Pe. 1..1
Информация о классе
ID
cim:GovHydroPID2
Тип
Class
Наследует
cim:TurbineGovernorDynamics
Свойств
22