GovHydroWPID Class
Woodward<sup>TM</sup> PID hydro governor. [Footnote: Woodward PID hydro governors are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]
Diagram
Свойства (22)
| ID | Тип | Описание | Количество |
|---|---|---|---|
| mwbase | ActivePower | Base for power values (<i>MWbase</i>) (> 0). Unit = MW. | 1..1 |
| treg | Seconds | Speed detector time constant (<i>Treg</i>) (>= 0). | 1..1 |
| reg | PU | Permanent drop (<i>Reg</i>). | 1..1 |
| kp | PU | Proportional gain (<i>Kp</i>). Typical value = 0,1. | 1..1 |
| ki | PU | Reset gain (<i>Ki</i>). Typical value = 0,36. | 1..1 |
| kd | PU | Derivative gain (<i>Kd</i>). Typical value = 1,11. | 1..1 |
| ta | Seconds | Controller time constant (<i>Ta</i>) (>= 0). Typical value = 0. | 1..1 |
| tb | Seconds | Gate servo time constant (<i>Tb</i>) (>= 0). Typical value = 0. | 1..1 |
| velmax | PU | Maximum gate opening velocity (<i>Velmax</i>) (> GovHydroWPID.velmin). Unit = PU / s. Typical value = 0. | 1..1 |
| velmin | PU | Maximum gate closing velocity (<i>Velmin</i>) (< GovHydroWPID.velmax). Unit = PU / s. Typical value = 0. | 1..1 |
| gatmax | PU | Gate opening limit maximum (<i>Gatmax</i>) (> GovHydroWPID.gatmin). | 1..1 |
| gatmin | PU | Gate opening limit minimum (<i>Gatmin</i>) (< GovHydroWPID.gatmax). | 1..1 |
| tw | Seconds | Water inertia time constant (<i>Tw</i>) (>= 0). Typical value = 0. | 1..1 |
| pmax | PU | Maximum power output (<i>Pmax</i>) (> GovHydroWPID.pmin). | 1..1 |
| pmin | PU | Minimum power output (<i>Pmin</i>) (< GovHydroWPID.pmax). | 1..1 |
| d | PU | Turbine damping factor (<i>D</i>). Unit = delta P / delta speed. | 1..1 |
| gv3 | PU | Gate position 3 (<i>Gv3</i>) (= 1,0). | 1..1 |
| gv1 | PU | Gate position 1 (<i>Gv1</i>). | 1..1 |
| pgv1 | PU | Output at <i>Gv1</i> PU of <i>MWbase</i> (<i>Pgv1</i>). | 1..1 |
| gv2 | PU | Gate position 2 (<i>Gv2</i>). | 1..1 |
| pgv2 | PU | Output at <i>Gv2</i> PU of <i>MWbase</i> (<i>Pgv2</i>). | 1..1 |
| pgv3 | PU | Output at <i>Gv3</i> PU of <i>MWbase</i> (<i>Pgv3</i>). | 1..1 |
Информация о классе
- ID
cim:GovHydroWPID- Тип
- Class
- Наследует
- cim:TurbineGovernorDynamics
- Свойств
- 22