GovSteamCC Class

Cross compound turbine governor. Unlike tandem compound units, cross compound units are not on the same shaft.

Diagram
Свойства (17)
ID Тип Описание Количество
mwbase ActivePower Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW. 1..1
pmaxhp PU Maximum HP value position (<i>Pmaxhp</i>). Typical value = 1. 1..1
rhp PU HP governor droop (<i>Rhp</i>) (&gt; 0). Typical value = 0,05. 1..1
t1hp Seconds HP governor time constant (<i>T1hp</i>) (&gt;= 0). Typical value = 0,1. 1..1
t3hp Seconds HP turbine time constant (<i>T3hp</i>) (&gt;= 0). Typical value = 0,1. 1..1
t4hp Seconds HP turbine time constant (<i>T4hp</i>) (&gt;= 0). Typical value = 0,1. 1..1
t5hp Seconds HP reheater time constant (<i>T5hp</i>) (&gt;= 0). Typical value = 10. 1..1
fhp PU Fraction of HP power ahead of reheater (<i>Fhp</i>). Typical value = 0,3. 1..1
dhp PU HP damping factor (<i>Dhp</i>). Typical value = 0. 1..1
pmaxlp PU Maximum LP value position (<i>Pmaxlp</i>). Typical value = 1. 1..1
rlp PU LP governor droop (<i>Rlp</i>) (&gt; 0). Typical value = 0,05. 1..1
t1lp Seconds LP governor time constant (<i>T1lp</i>) (&gt;= 0). Typical value = 0,1. 1..1
t3lp Seconds LP turbine time constant (<i>T3lp</i>) (&gt;= 0). Typical value = 0,1. 1..1
t4lp Seconds LP turbine time constant (<i>T4lp</i>) (&gt;= 0). Typical value = 0,1. 1..1
t5lp Seconds LP reheater time constant (<i>T5lp</i>) (&gt;= 0). Typical value = 10. 1..1
flp PU Fraction of LP power ahead of reheater (<i>Flp</i>). Typical value = 0,7. 1..1
dlp PU LP damping factor (<i>Dlp</i>). Typical value = 0. 1..1
Информация о классе
ID
cim:GovSteamCC
Тип
Class
Наследует
cim:CrossCompoundTurbineGovernorDynamics
Свойств
17