GovSteamFV2 Class

Steam turbine governor with reheat time constants and modelling of the effects of fast valve closing to reduce mechanical power.

Diagram
Свойства (12)
ID Тип Описание Количество
mwbase ActivePower Alternate base used instead of machine base in equipment model if necessary (<i>MWbase</i>) (&gt; 0). Unit = MW. 1..1
t1 Seconds Governor time constant (<i>T1</i>) (&gt;= 0). 1..1
vmax PU (<i>Vmax</i>) (&gt; GovSteamFV2.vmin). 1..1
vmin PU (<i>Vmin</i>) (&lt; GovSteamFV2.vmax). 1..1
k PU Fraction of the turbine power developed by turbine sections not involved in fast valving (<i>K</i>). 1..1
t3 Seconds Reheater time constant (<i>T3</i>) (&gt;= 0). 1..1
dt PU (<i>Dt</i>). 1..1
tt Seconds Time constant with which power falls off after intercept valve closure (<i>Tt</i>) (&gt;= 0). 1..1
r PU (<i>R</i>). 1..1
ta Seconds Time after initial time for valve to close (<i>Ta</i>) (&gt;= 0). 1..1
tb Seconds Time after initial time for valve to begin opening (<i>Tb</i>) (&gt;= 0). 1..1
tc Seconds Time after initial time for valve to become fully open (<i>Tc</i>) (&gt;= 0). 1..1
Информация о классе
ID
cim:GovSteamFV2
Тип
Class
Наследует
cim:TurbineGovernorDynamics
Свойств
12