TurbLCFB1 Class

Turbine load controller model developed by WECC. This model represents a supervisory turbine load controller that acts to maintain turbine power at a set value by continuous adjustment of the turbine governor speed-load reference. This model is intended to represent slow reset 'outer loop' controllers managing the action of the turbine governor.

Diagram
Свойства (12)
ID Тип Описание Количество
mwbase ActivePower Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW. 1..1
speedReferenceGovernor Boolean Type of turbine governor reference (<i>Type</i>). true = speed reference governor false = load reference governor. Typical value = true. 1..1
db PU Controller deadband (<i>db</i>). Typical value = 0. 1..1
emax PU Maximum control error (<i>Emax</i>) (see parameter detail 4). Typical value = 0,02. 1..1
fb PU Frequency bias gain (<i>Fb</i>). Typical value = 0. 1..1
kp PU Proportional gain (<i>Kp</i>). Typical value = 0. 1..1
ki PU Integral gain (<i>Ki</i>). Typical value = 0. 1..1
fbf Boolean Frequency bias flag (<i>Fbf</i>). true = enable frequency bias false = disable frequency bias. Typical value = false. 1..1
pbf Boolean Power controller flag (<i>Pbf</i>). true = enable load controller false = disable load controller. Typical value = false. 1..1
tpelec Seconds Power transducer time constant (<i>Tpelec</i>) (&gt;= 0). Typical value = 0. 1..1
irmax PU Maximum turbine speed/load reference bias (<i>Irmax</i>) (see parameter detail 3). Typical value = 0. 1..1
pmwset ActivePower Power controller setpoint (<i>Pmwset</i>) (see parameter detail 1). Unit = MW. Typical value = 0. 1..1
Информация о классе
ID
cim:TurbLCFB1
Тип
Class
Наследует
cim:TurbineLoadControllerDynamics
Свойств
12