GovGAST1 Class

Modified single shaft gas turbine.

Diagram
Свойства (34)
ID Тип Описание Количество
mwbase ActivePower Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW. 1..1
r PU Permanent droop (<i>R</i>) (&gt;0). Typical value = 0,04. 1..1
t1 Seconds Governor mechanism time constant (<i>T1</i>) (&gt;= 0). <i>T1</i> represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical value = 0,5. 1..1
t2 Seconds Turbine power time constant (<i>T2</i>) (&gt;= 0). <i>T2</i> represents delay due to internal energy storage of the gas turbine engine. <i>T2</i> can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of the free power turbine of an aero-derivative unit, for example. Typical value = 0,5. 1..1
t3 Seconds Turbine exhaust temperature time constant (<i>T3</i>) (&gt;= 0). <i>T3</i> represents delay in the exhaust temperature and load limiting system. Typical value = 3. 1..1
lmax PU Ambient temperature load limit (<i>Lmax</i>). <i>Lmax</i> is the turbine power output corresponding to the limiting exhaust gas temperature. Typical value = 1. 1..1
kt PU Temperature limiter gain (<i>Kt</i>). Typical value = 3. 1..1
vmax PU Maximum turbine power, PU of MWbase (<i>Vmax</i>) (&gt; GovGAST1.vmin). Typical value = 1. 1..1
vmin PU Minimum turbine power, PU of MWbase (<i>Vmin</i>) (&lt; GovGAST1.vmax). Typical value = 0. 1..1
fidle PU Fuel flow at zero power output (<i>Fidle</i>). Typical value = 0,18. 1..1
rmax Float Maximum fuel valve opening rate (<i>Rmax</i>). Unit = PU / s. Typical value = 1. 1..1
loadinc PU Valve position change allowed at fast rate (<i>Loadinc</i>). Typical value = 0,05. 1..1
tltr Seconds Valve position averaging time constant (<i>Tltr</i>) (&gt;= 0). Typical value = 10. 1..1
ltrate Float Maximum long term fuel valve opening rate (<i>Ltrate</i>). Typical value = 0,02. 1..1
a Float Turbine power time constant numerator scale factor (<i>a</i>). Typical value = 0,8. 1..1
b Float Turbine power time constant denominator scale factor (<i>b</i>) (&gt;0). Typical value = 1. 1..1
db1 Frequency Intentional dead-band width (<i>db1</i>). Unit = Hz. Typical value = 0. 1..1
eps Frequency Intentional db hysteresis (<i>eps</i>). Unit = Hz. Typical value = 0. 1..1
db2 ActivePower Unintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0. 1..1
gv1 PU Nonlinear gain point 1, PU gv (<i>Gv1</i>). Typical value = 0. 1..1
pgv1 PU Nonlinear gain point 1, PU power (<i>Pgv1</i>). Typical value = 0. 1..1
gv2 PU Nonlinear gain point 2,PU gv (<i>Gv2</i>). Typical value = 0. 1..1
pgv2 PU Nonlinear gain point 2, PU power (<i>Pgv2</i>). Typical value = 0. 1..1
gv3 PU Nonlinear gain point 3, PU gv (<i>Gv3</i>). Typical value = 0. 1..1
pgv3 PU Nonlinear gain point 3, PU power (<i>Pgv3</i>). Typical value = 0. 1..1
gv4 PU Nonlinear gain point 4, PU gv (<i>Gv4</i>). Typical value = 0. 1..1
pgv4 PU Nonlinear gain point 4, PU power (<i>Pgv4</i>). Typical value = 0. 1..1
gv5 PU Nonlinear gain point 5, PU gv (<i>Gv5</i>). Typical value = 0. 1..1
pgv5 PU Nonlinear gain point 5, PU power (<i>Pgv5</i>). Typical value = 0. 1..1
gv6 PU Nonlinear gain point 6, PU gv (<i>Gv6</i>). Typical value = 0. 1..1
pgv6 PU Nonlinear gain point 6, PU power (<i>Pgv6</i>). Typical value = 0. 1..1
ka PU Governor gain (<i>Ka</i>). Typical value = 0. 1..1
t4 Seconds Governor lead time constant (<i>T4</i>) (&gt;= 0). Typical value = 0. 1..1
t5 Seconds Governor lag time constant (<i>T5</i>) (&gt;= 0). If = 0, entire gain and lead-lag block is bypassed. Typical value = 0. 1..1
Информация о классе
ID
cim:GovGAST1
Тип
Class
Наследует
cim:TurbineGovernorDynamics
Свойств
34