GovHydro3 Class

Modified IEEE hydro governor-turbine. This model differs from that defined in the IEEE modelling guideline paper in that the limits on gate position and velocity do not permit "wind up" of the upstream signals.

Diagram
Свойства (36)
ID Тип Описание Количество
mwbase ActivePower Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW. 1..1
pmax PU Maximum gate opening, PU of MWbase (<i>Pmax</i>) (&gt; GovHydro3.pmin). Typical value = 1. 1..1
pmin PU Minimum gate opening, PU of <i>MWbase</i> (<i>Pmin</i>) (&lt; GovHydro3.pmax). Typical value = 0. 1..1
governorControl Boolean Governor control flag (<i>Cflag</i>). true = PID control is active false = double derivative control is active. Typical value = true. 1..1
rgate PU Steady-state droop, PU, for governor output feedback (<i>Rgate</i>). Typical value = 0. 1..1
relec PU Steady-state droop, PU, for electrical power feedback (<i>Relec</i>). Typical value = 0,05. 1..1
td Seconds Input filter time constant (<i>Td</i>) (&gt;= 0). Typical value = 0,05. 1..1
tf Seconds Washout time constant (<i>Tf</i>) (&gt;= 0). Typical value = 0,1. 1..1
tp Seconds Gate servo time constant (<i>Tp</i>) (&gt;= 0). Typical value = 0,05. 1..1
velop Float Maximum gate opening velocity (<i>Velop</i>). Unit = PU / s. Typical value = 0,2. 1..1
velcl Float Maximum gate closing velocity (<i>Velcl</i>). Unit = PU / s. Typical value = -0,2. 1..1
k1 PU Derivative gain (<i>K1</i>). Typical value = 0,01. 1..1
k2 PU Double derivative gain, if <i>Cflag</i> = -1 (<i>K2</i>). Typical value = 2,5. 1..1
ki PU Integral gain (<i>Ki</i>). Typical value = 0,5. 1..1
kg PU Gate servo gain (<i>Kg</i>). Typical value = 2. 1..1
tt Seconds Power feedback time constant (<i>Tt</i>) (&gt;= 0). Typical value = 0,2. 1..1
db1 Frequency Intentional dead-band width (<i>db1</i>). Unit = Hz. Typical value = 0. 1..1
eps Frequency Intentional db hysteresis (<i>eps</i>). Unit = Hz. Typical value = 0. 1..1
db2 ActivePower Unintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0. 1..1
tw Seconds Water inertia time constant (<i>Tw</i>) (&gt;= 0). If = 0, block is bypassed. Typical value = 1. 1..1
at PU Turbine gain (<i>At</i>) (&gt;0). Typical value = 1,2. 1..1
dturb PU Turbine damping factor (<i>Dturb</i>). Typical value = 0,2. 1..1
qnl PU No-load turbine flow at nominal head (<i>Qnl</i>). Typical value = 0,08. 1..1
h0 PU Turbine nominal head (<i>H0</i>). Typical value = 1. 1..1
gv1 PU Nonlinear gain point 1, PU gv (<i>Gv1</i>). Typical value = 0. 1..1
pgv1 PU Nonlinear gain point 1, PU power (<i>Pgv1</i>). Typical value = 0. 1..1
gv2 PU Nonlinear gain point 2, PU gv (<i>Gv2</i>). Typical value = 0. 1..1
pgv2 PU Nonlinear gain point 2, PU power (<i>Pgv2</i>). Typical value = 0. 1..1
gv3 PU Nonlinear gain point 3, PU gv (<i>Gv3</i>). Typical value = 0. 1..1
pgv3 PU Nonlinear gain point 3, PU power (<i>Pgv3</i>). Typical value = 0. 1..1
gv4 PU Nonlinear gain point 4, PU gv (<i>Gv4</i>). Typical value = 0. 1..1
pgv4 PU Nonlinear gain point 4, PU power (<i>Pgv4</i>). Typical value = 0. 1..1
gv5 PU Nonlinear gain point 5, PU gv (<i>Gv5</i>). Typical value = 0. 1..1
pgv5 PU Nonlinear gain point 5, PU power (<i>Pgv5</i>). Typical value = 0. 1..1
gv6 PU Nonlinear gain point 6, PU gv (<i>Gv6</i>). Typical value = 0. 1..1
pgv6 PU Nonlinear gain point 6, PU power (<i>Pgv6</i>). Typical value = 0. 1..1
Информация о классе
ID
cim:GovHydro3
Тип
Class
Наследует
cim:TurbineGovernorDynamics
Свойств
36