GovHydroPID Class

PID governor and turbine.

Diagram
Свойства (33)
ID Тип Описание Количество
mwbase ActivePower Base for power values (<i>MWbase</i>) (&gt; 0). Unit = MW. 1..1
pmax PU Maximum gate opening, PU of MWbase (<i>Pmax</i>) (&gt; GovHydroPID.pmin). Typical value = 1. 1..1
pmin PU Minimum gate opening, PU of MWbase (<i>Pmin</i>) (&lt; GovHydroPID.pmax). Typical value = 0. 1..1
r PU Steady state droop (<i>R</i>). Typical value = 0,05. 1..1
td Seconds Input filter time constant (<i>Td</i>) (&gt;= 0). If = 0, block is bypassed. Typical value = 0. 1..1
tf Seconds Washout time constant (<i>Tf</i>) (&gt;= 0). Typical value = 0,1. 1..1
tp Seconds Gate servo time constant (<i>Tp</i>) (&gt;= 0). If = 0, block is bypassed. Typical value = 0,35. 1..1
velop Float Maximum gate opening velocity (<i>Velop</i>). Unit = PU / s. Typical value = 0,09. 1..1
velcl Float Maximum gate closing velocity (<i>Velcl</i>). Unit = PU / s. Typical value = -0,14. 1..1
kd PU Derivative gain (<i>Kd</i>). Typical value = 1,11. 1..1
kp PU Proportional gain (<i>Kp</i>). Typical value = 0,1. 1..1
ki PU Integral gain (<i>Ki</i>). Typical value = 0,36. 1..1
kg PU Gate servo gain (<i>Kg</i>). Typical value = 2,5. 1..1
tturb Seconds Turbine time constant (<i>Tturb</i>) (&gt;= 0). See Parameter detail 3. Typical value = 0,8. 1..1
aturb PU Turbine numerator multiplier (<i>Aturb</i>) (see parameter detail 3). Typical value -1. 1..1
bturb PU Turbine denominator multiplier (<i>Bturb</i>) (see parameter detail 3). Typical value = 0,5. 1..1
tt Seconds Power feedback time constant (<i>Tt</i>) (&gt;= 0). If = 0, block is bypassed. Typical value = 0,02. 1..1
db1 Frequency Intentional dead-band width (<i>db1</i>). Unit = Hz. Typical value = 0. 1..1
inputSignal Boolean Input signal switch (<i>Flag</i>). true = <i>Pe</i> input is used false = feedback is received from <i>CV</i>. <i>Flag</i> is normally dependent on <i>Tt</i>. If <i>Tt </i>is zero, <i>Flag</i> is set to false. If <i>Tt</i> is not zero, <i>Flag</i> is set to true. Typical value = true. 1..1
eps Frequency Intentional db hysteresis (<i>eps</i>). Unit = Hz. Typical value = 0. 1..1
db2 ActivePower Unintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0. 1..1
gv1 PU Nonlinear gain point 1, PU gv (<i>Gv1</i>). Typical value = 0. 1..1
pgv1 PU Nonlinear gain point 1, PU power (<i>Pgv1</i>). Typical value = 0. 1..1
gv2 PU Nonlinear gain point 2, PU gv (<i>Gv2</i>). Typical value = 0. 1..1
pgv2 PU Nonlinear gain point 2, PU power (<i>Pgv2</i>). Typical value = 0. 1..1
gv3 PU Nonlinear gain point 3, PU gv (<i>Gv3</i>). Typical value = 0. 1..1
pgv3 PU Nonlinear gain point 3, PU power (<i>Pgv3</i>). Typical value = 0. 1..1
gv4 PU Nonlinear gain point 4, PU gv (<i>Gv4</i>). Typical value = 0. 1..1
pgv4 PU Nonlinear gain point 4, PU power (<i>Pgv4</i>). Typical value = 0. 1..1
gv5 PU Nonlinear gain point 5, PU gv (<i>Gv5</i>). Typical value = 0. 1..1
pgv5 PU Nonlinear gain point 5, PU power (<i>Pgv5</i>). Typical value = 0. 1..1
gv6 PU Nonlinear gain point 6, PU gv (<i>Gv6</i>). Typical value = 0. 1..1
pgv6 PU Nonlinear gain point 6, PU power (<i>Pgv6</i>). Typical value = 0. 1..1
Информация о классе
ID
cim:GovHydroPID
Тип
Class
Наследует
cim:TurbineGovernorDynamics
Свойств
33